THE FOLLOWING COMPONENTS SHIP FROM GREENHECK WITH HRE (INSTALLATION, WIRING, AND POWER BY OTHERS) |
| |||
PART DESCRIPTIONS | GREENHECK P/N | QTY. | HOLDING VA | INRUSH VA |
JOHNSON CONTROLLER | 07458032 | 1 | - | - |
OUTDOOR AIR SENSOR | 07458298 | 1 | - | - |
24 HOUR TIMER | 07381940 | 1 | - | - |
VALVE, WATER SUPPLY (A) | 05461262 | 1 | 25 | 70 |
VALVE, DRAIN (B) | 05461263 | 1 | 25 | 50 |
VALVE, SUMP DRAIN (C) | 05461264 | 1 | 25 | 70 |
24V AC POWER AND WIRING
BY OTHERS
OUTDOOR AIR
SENSOR
| 24VAC | SENSOR | COM | |
|
| JOHNSON CONTROLLER |
| |
|
| JC |
| |
| 15 | TIMER | A2 | |
JC | B1 | 16 | ||
T1 | ||||
| A1 | 18 | ||
|
| |||
NC | COM |
|
| |
| SIDE OF HRE UNIT |
|
| |
DRAIN TRAP | SUMP DRAIN PIPE |
|
| |
(TO EACH EVAP) |
|
|
OUTDOOR AIR SENSOR
| TIMER | |
VA | VALVE "A" | |
1/2 PIPE SIZE (NC) | ||
| ||
VB | VALVE "B" | |
1/4 PIPE SIZE (NO) | ||
| ||
VC | VALVE "C" | |
3/4 PIPE SIZE (NO) | ||
|
Cooling coils are provided with a stainless steel drain pan with
To ensure the drain trap works properly, the trap height must account for the difference in static pressure between ambient conditions outside the unit and the internal
negative pressure of the cooling coil compartment.. For energy recovery units, an assumption of 3..0 in.. wg.. differential will be sufficient.. This would require a trap design as shown.. If the internal static is believed to be higher, consult factory..
Refer to local codes to determine drainage requirements.. If draining onto to roof, place a drip pad below drain to protect
roof.. If draining onto roof is not acceptable, a drain line must be attached to the trap.. The drain line must be pitched away from
the unit at least
Drainage problems not only occur from improper drain trap design, but also from lack of maintenance of the cooling coil compartment.. Algae can form in the drain pan and trap and cause reduced water flow, which can in turn result in backup into the system.. Regular maintenance will prevent this from occurring.. If the drains have a cleanout opening, be sure to close the opening after cleaning..