Greenheck Fan SE1 Backdraft Dampers, Volume Control/Heavy Duty Dampers, Damper Type, Description

Models: SE1 SS1

1 40
Download 40 pages 7.21 Kb
Page 11
Image 11
Backdraft Dampers

Backdraft Dampers

Used alone or in conjunction with the wall housing or wall collar, backdraft dampers are available for exhaust or supply configurations. Backdraft dampers are constructed with galvanized frames, aluminum blades and vinyl blade seals. Actuators are available in 24, 120, 208, 230 or 460 volts. Actuators for 50 cycle voltages are also available. Actuators for 50 cycle voltages are also available.

Damper Type

 

Description

Flush Exterior

Flush Interior

Exhaust - Gravity or Motorized¹

WD-320 and WD-300

Exhaust backdraft dampers

For applications where the

 

 

exhaust dampers are

are Model WD-320, which

mounting flange is required

 

 

available as either gravity

has the prepunched

on the inlet end of the

 

 

operated or motorized

mounting flange located

damper (so that the damper

 

 

 

on the outlet end of the

projects to the exterior), the

 

 

 

damper for a flush exterior

Model WD-300 is available.

Airflow

Airflow

 

appearance.

 

Wall Housing Installation

 

Wall Installation

Model WD-320 shown

 

 

 

Supply – Gravity²

 

 

WD-430 and WD-420

• Model WD-430 has a

• Model WD-420 is for

 

 

 

 

intake dampers are

 

prepunched mounting

applications where a

 

 

 

 

only available as gravity

 

flange located on the inlet

prepunched mounting

 

 

 

 

operated

 

end of the damper for a

flange is required on the

 

 

 

Galvanized steel frame

 

flush exterior appearance

outlet end of damper (so

 

 

 

 

 

the damper projects to

 

Airflow

Airflow

 

and aluminum blades

Flange on intake

 

 

 

 

the exterior)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Flange on discharge

Wall Housing Installation

Wall Installation

Model WD-430 shown

 

 

 

Supply - Motorized³

 

WD-220 and WD-210

• Model WD-220 has a

• Model WD-210 is for

 

 

 

 

intake dampers are only

 

prepunched mounting

applications where

 

 

 

 

available as motorized

 

flange located on the inlet

a mounting flange is

 

 

 

Galvanized steel frame

 

end of the damper for a

required on the outlet end

 

 

 

 

flush exterior appearance

of the damper (so that

 

 

 

 

and aluminum blades

 

 

Airflow

 

 

 

 

the damper projects to

 

Airflow

 

 

 

 

 

 

 

 

 

Flange located opposite

the exterior)

 

 

 

 

 

 

of motor side of the

• Flange located on motor

 

 

 

 

 

 

damper

side of the damper

 

 

 

 

Wall Housing Installation

Wall Installation

Model WD-220 shown

Volume Control/Heavy Duty Dampers

Volume control dampers are available for exhaust or supply configurations and may be used alone or in conjunction with the wall housing or wall collar. Constructed with heavy galvanized steel frames and blades, model VCD dampers are designed to handle higher air volumes than the standard backdraft damper. Dampers are available in standard leakage (VCD-20), low leakage (VCD-23) and insulated low leakage (VCD-34) configurations. Actuators are available in 24, 120, 208, 230 or 460 volts. Actuators for 50 cycle voltages are also available.

Damper Type

Description

Flush Exterior
Flush Interior
Exhaust or Supply - Motorized

Model VCD-20- Standard leakage

The VCD damper has the

N/A

 

Model VCD-23 - Low leakage

parallel blade set-up and

 

 

a prepunched mounting

 

 

This damper has blade and jamb

 

 

flange that provides a flush

 

 

seals for minimal leakage when

 

 

exterior appearance.

 

 

closed.

 

 

 

 

Airflow

Model VCD-34- Insulated low

 

 

 

 

 

 

leakage – This damper has blade

 

 

 

and jamb seals for minimal

 

 

Airflow

leakage when closed. Blades are

 

 

 

constructed with 12 in. (13 mm)

 

 

 

polystyrene insulation between two

 

 

Wall Housing Installation Wall Installation

galvanized steel skins.

 

 

¹ Model WD-320 and WD-300 are used with fans where the motor is 5 hp or less. For fans with motors larger than 5 hp, the Model GM-31 medium duty gravity backdraft damper or the Model VCD heavy duty motorized backdraft dampers are required.

² Model WD-430 and WD-420 are used with fans where the motor is 5 hp or less. For fans with motors larger than 5 hp, the Model VCD heavy duty motorized backdraft dampers are required.

³Model WD-220 and WD-210 are used with fans where the motor is 3 hp or less. For fans with motors larger than 3 hp, the Model VCD heavy duty motorized backdraft damper is required.

Note: Wall housing length increases by 6 inches (152 mm) when a heavy duty backdraft damper is specified.

11

Page 11
Image 11
Greenheck Fan SE1, SS1 manual Backdraft Dampers, Volume Control/Heavy Duty Dampers, Damper Type, Description, Flush Exterior