Greenheck Fan SS1, SE1 Filtered Supply Wall Housing Mounting Options, Weatherhood, Damper Guard

Models: SE1 SS1

1 40
Download 40 pages 7.21 Kb
Page 10
Image 10
Filtered Supply Wall Housing

Filtered Supply Wall Housing

Mounting Options

Filtered supply wall housings are available in seven sizes for fans ranging from size 24 to 54 inches (610 to 1372 mm). They are designed with the draw-thru concept to achieve the highest filter and fan efficiencies.

Standard construction is galvanized steel (painted steel optional). Mounting flanges are factory installed for either flush exterior or flush interior. Permanent 2 inch (51 mm) washable filters are accessed through a bolted panel and can be easily removed for cleaning.

All accessory items available with the standard wall housing can be used with the filtered supply wall housing.

Diffusers - Wall Housing Mounted - Manual Operator

 

 

 

Diffusers are constructed with heavy gauge galvanized steel frames,

 

 

 

blades and prepunched mounting flanges. They are designed to mount to

 

 

 

the interior end of the wall housing when used in the supply configuration.

 

 

Manual quadrants set the angle of the blades to deflect air in 1, 2 or 4

 

 

 

directions.

 

 

 

 

 

 

 

Angles

 

 

 

 

 

 

 

Closure Angles

 

Mounting

 

 

 

 

 

 

 

 

 

Closure Angles

 

 

 

 

INTERIOR

Wall

EXTERIOR

 

 

 

 

 

 

 

 

 

 

 

 

An extra set of mounting flanges is available for field installation to close

 

 

 

off the interior wall opening for a finished appearance.

 

 

 

 

Size

A

B

C

Wall Opening

Filter Size & Quantity

Notes:

 

 

1. Additional bracing (by others) above or below the

24

3214 (819)

63 (1600)

24 (610)

3334 (857)

(4)

2314 (591) x 1614 (413)

housing is required for support of the filtered supply

30

3814 (972)

65 (1651)

26 (660)

3934 (1010)

(4)

2458 (625) x 1914 (489)

wall housing.

 

 

36

4414 (1124)

6714 (1708)

2814 (718)

4534 (1162)

(6)

2314 (591) x 2218 (562)

Attach at least two supports (either vertical or angled)

42

5018 (1273)

7278 (1851)

34 (864)

5134 (1314)

(6)

2418 (613) x 2518 (638)

to the end of housing.

 

 

Vertical supports must carry 500# minimum per

48

5618 (1426)

7278 (1851)

34 (864)

5734 (1467)

(12)

2314 (591) x 1834 (476)

support, and angled (45°) supports a minimum of 750#

54

6238 (1584)

791116 (2024)

401116 (1033)

6334 (1619)

(12)

2314 (591) x 2034 (527)

per support.

 

 

2. Filtered supply wall housing, fan damper and guards

Filters are 2 in (51 mm) nominal thickness. Above filter sizes are actual dimensions. All dimensions given in

ship completely factory assembled. Weatherhood

inches (mm).

 

 

 

 

 

ships loose.

 

 

Weatherhood

Weatherhoods shield wall openings and dampers from rain and snow. Weatherhoods are shipped unassembled in kit form for field assembly. Construction is of galvanized steel with wire mesh birdscreen. Mounting flanges have prepunched mounting holes. 45° turn down is for exhaust and 90° turn down is for exhaust and supply. Options include aluminum construction, insect screen and painted finish.

Damper Guard

Damper guards meet the OSHA requirements completely enclose the damper or wall openings on the discharge side of the fan. They are constructed of expanded galvanized steel screen in galvanized steel frames. Mounting flanges have prepunched mounting holes. Options include aluminum construction and painted finish.

Dampers

Used alone or in conjunction with the wall housing or wall collar, a complete line of dampers is available for exhaust or supply configurations

FILTERED SUPPLY FAN in Wall Housing with Filter

Bank, Gravity Damper and Weatherhood

Note: This chart is for manual calculations only. CAPS has filter losses built into the selection tool when the filtered housing option is selected.

10

Page 10
Image 10
Greenheck Fan SS1, SE1 Filtered Supply Wall Housing Mounting Options, Diffusers - Wall Housing Mounted - Manual Operator