Greenheck Fan SE1, SS1 manual Belt Drive Specifications, Reversible Belt Drive

Models: SE1 SS1

1 40
Download 40 pages 7.21 Kb
Page 39
Image 39
Belt Drive Specifications

Belt Drive Specifications

Belt Drive

Belt driven, axial type sidewall fans shall be provided as follows:

Propellers shall be constructed with fabricated steel, fabricated aluminum, or cast aluminum blades and hubs. Propellers shall be securely attached to fan shafts. All propellers shall be statically and dynamically balanced to AMCA standard 204-05.

Motors shall be permanently lubricated, heavy duty type, carefully matched to the fan load and furnished at the specified voltage, phase, and enclosure.

Ground and polished steel fan shafts shall be mounted in permanently lubricated, sealed ball bearing pillow blocks and coated with an anti-corrosive coating. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours (L50 average life of 500,000 hours) at maximum cataloged operating speeds. Drives shall be sized for a minimum of 150 percent of driven horsepower. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to wheel and motor shafts. Motor sheaves shall be adjustable for system balancing.

Drive frame and panel assemblies shall be galvanized steel or painted steel. Drive frames shall be formed channels and fan panels shall have prepunched mounting holes, formed flanges, and a deep formed inlet venturi. Drive frames and panels shall be bolted construction or welded construction (level 3 fans only).

The axial exhaust or supply fans shall bear the AMCA Certified Ratings Seals for both sound and air performance.

Fans shall be Model SBE-1, SBE-2, SBE-3, SBS-1, SBS-2, SBS-3, SBCE and SBCS as manufactured by Greenheck, Schofield, Wisconsin.

Reversible Belt Drive

Belt driven, axial type sidewall fans shall be provided as follows:

Propellers shall be constructed with cast aluminum blades and hubs. Propellers shall be securely attached to fan shafts. All propellers shall be statically and dynamically balanced to AMCA standard 204-05.

Motors shall be permanently lubricated, heavy duty type, carefully matched to the fan load and furnished at the specified voltage, phase, and enclosure.

Ground and polished steel fan shafts shall be mounted in permanently lubricated, sealed ball bearing pillow blocks, and coated with an anti-corrosive coating. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours (L50 average life of 500,000) at maximum cataloged operating speeds. Drives shall be sized for a minimum of 150 percent of driven horsepower. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to wheel and motor shafts. Motor sheaves shall be adjustable for system balancing.

Drive frame and panel assemblies shall be galvanized steel or painted steel. Drive frames shall be formed channels and fan panels shall have prepunched mounting holes, formed flanges, and a deep formed double inlet venturi. Drive frames and panels shall be bolted construction or welded construction.

The axial exhaust or supply fans shall be tested in accordance AMCA Standard 301 in both sound and air performance.

Fans shall be Model SBCR as manufactured by Greenheck, Schofield, Wisconsin.

39

Page 39
Image 39
Greenheck Fan SE1, SS1 manual Belt Drive Specifications, Reversible Belt Drive