SECTION 2: CIRCUIT REQUIREMENTS

220V Operation

 

Grounding

 

 

 

 

 

 

The Model G8621 Shaper is furnished with a 3450 R.P.M., 5 H.P., Single-Phase 220V motor, push-button ON/OFF magnetic starter switch, for- ward-reverse switch and a cord set. Under nor- mal use, the motor draws approximately 25 amps

@220V. We recommend a 30 amp circuit break- er. If frequent circuit failures occur when using the shaper, contact our service department.

The shaper motor must be connected to its own dedicated 30A circuit. The shaper should not share a circuit with any other machine, and the wires in the circuit should be rated for 30A. A standard 2-pole breaker is also necessary for use with the shaper.

We recommend using a NEMA-style L6-30 plug and outlet similar to that in Figure 1. You may also “hard-wire” the shaper directly to your panel, provided you place a disconnect near the machine. Check the electrical codes in your area for specifics on wiring requirements.

In the event of an electrical short, grounding reduces the risk of electric shock by providing a path of least resistance to disperse electric cur- rent. This tool is equipped with an electric cord that has an equipment-grounding conductor which must be properly connected to a grounding plug. The plug must be plugged into a matching outlet that is properly installed and grounded in accordance with all local codes and ordinances.

Improper connections of the electrical-grounding conductor can result in the risk of electric shock. The conductor with green or green and yellow striped insulation is the electrical-grounding con- ductor. If repair or replacement of the electric cord or plug is necessary, do not connect the equipment grounding conductor to a live terminal.

This equipment must be grounded. Verify that any existing electrical outlet and circuit you intend to plug into is actually grounded. Under no cir- cumstances should the grounding pin from any three-pronged plug be removed. Serious injury may occur.

Figure 1. 220V Single-Phase

G8621 Heavy-Duty Sliding Table Shaper

-5-