Image 29
6. INSTALLATION OF WATER DRAINAGE PIPE
Large size seal pad 10
(accessory)
4mm below below500
Table 1

Installation Procedure

5. REFRIGERANT PIPING (As for outdoor piping, please refer to installation Manual of outdoor unit.)

<Cautions for the drain water lifting pipe> Outdoor is precharged with refrigerant.

Manual background Be sure to see the Fig.1, when connecting and removing piping from unit.

Manual background For the size of the flare nut, please refer to Table 1.

Manual background Apply refrigerant oil at both inside and outsid of l flare nut. Tighten it band tight 3-4 turns then tighten it.

Manual background Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).

Manual background Check piping joints for gas leakage. Insulate piping as shown in Fig. below. Manual background Cover joint of gas piping and insulator 7 with seal.

Apple refrigerant oil

Medium size seal pad(accessory) 11

 

(Cover the piping joint

 

 

with seal pad.)

 

Torque spanner

Clamp 3

 

 

 

spanner

Insulator(accessory) 8

(For liquid pipe)

 

 

Piping joing

 

Insulator(accessory) 7

Gas pipe

(For gas pipe)

Flare nut

Liquid pipe

 

Pipe

Tighten

A(mm)

 

Flare shape

size

torque

 

 

 

 

 

6.35 1420~1720N.cm

8.3~8.7

 

 

 

 

(144~176kgf.cm)

 

 

 

 

9.52

3270~3990N.cm 12.0~12.4

 

 

 

(333~407kgf.cm)

 

 

2

R0.4 ~ 0.8

 

4950~6030N.cm 15.4~15.8

0.5

12.7

45

 

(504~616kgf.cm)

 

90

A

 

6180~7540N.cm

18.6~19.0

 

 

 

 

 

15.88 (630~770kgf.cm)

 

 

 

 

19.05 9720~11860N.cm

22.9~23.3

 

 

 

 

(990~1210kgf.cm)

 

 

 

 

6. INSTALLATION OF WATER DRAINAGE PIPE

(1) Install water drainage pipe

Manual background Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm)

Manual background Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.

Manual background If downward slope can't be made, take other measures to lift it up.

Manual background Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.

1-1.5m

Slope over 1/100

Use the self-provided stiff pipe and clamp 1 with unit. Insert water pipe into water plug until it reaches the white tape. Tighten the clip until head of the screw is less than 4mm from hose.

Wind the drain hose to the clip using seal pad 9 . Insulate drain hose in the room.

Tape (White)

Clamp

Clamp (accessory)

Self-provided stiff pipe

<Cautions for the drain water lifting pipe>

Manual background Installation height shall be less than 280mm.

Manual background There should be a right angle with unit, 300mm from unit.

 

300mm below 1~1.5m

Suspending bracket

Drain hose

 

below280220

below500

(accessory)

 

drain water lifting pipe

 

Self-provided stiff pipe

(accessory) Manual backgroundManual backgroundManual backgroundManual background below75

(Note)

Clamp (accessory)

Manual background The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it. Manual background If several water hoses join together, do as per following proceedures.

Over 100Manual background

Connect water hoses with a T joint.

Specifieations of the water hoses shall meet the requirements for the unit running.

27