Haier AC142XCERA Trouble Shooting, Abnormal communication, between wired controller and

Models: AC142XCERA AC182XCERA

1 26
Download 26 pages 58.44 Kb
Page 25
Image 25
Abnormal communication

between wired controller and Trouble Shooting

 

 

FAILURE CODE

 

 

 

 

TROUBLE SHOOTING

(TIMER LED OF INDOOR

POSSIBLE REASONS

 

 

RECEIVER BOARD FLASHES

 

 

 

 

TIMES)

 

 

 

 

Faulty temperature sensor Tai

ONCE

*

Sensor disconnected, or broken, or at wrong

 

position, or short circuit

 

 

 

 

 

 

 

 

 

Faulty temperature sensor Tc1

TWICE

*

Sensor disconnected, or broken, or at wrong

 

position, or short circuit

 

 

 

Faulty temperature sensor Tc2

3 TIMES

*

Sensor disconnected, or broken, or at wrong

 

position, or short circuit

 

 

 

 

 

 

 

Faulty temperature sensor Tm

4 TIMES

*

Sensor disconnected, or broken, or at wrong

 

position, or short circuit

 

Faulty EEPROM on indoor

5 TIMES

 

Faulty indoor unit PCB

 

unit PCB

 

 

 

 

 

 

 

Abnormal communication

 

 

Wrong connection, or the wires be disconnected,

 

6 TIMES

*

or wrong address setting of indoor units, or faulty

 

between indoor and outdoor unit

 

 

 

 

power supply or faulty PCB

 

Abnormal communication

7 TIMES

 

Wrong connection, or use the wired controllerbe

 

between wired controller and

*

 

disconnected, faulty PCB

 

indoor unit PCB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pump motor disconnected, or at wrong

 

Drainage system abnormal

8 TIMES

*

position, or the float switch broken down

 

 

or the float switch disconnected,or at

 

 

 

 

wrong position

 

 

 

 

 

 

 

Indoor unit address repeated

9 TIMES

 

Wrong setting of indoor unit address

 

 

 

 

 

 

 

Abnormal communication

14 TIMES *

Faulty indoor unit PCB

 

between chip TMP/807 and

 

chip TMP/846

 

 

 

 

Malfunction on outdoor unit

20 TIMES

Check the outdoor unit failure code

Note:

1.Please contact the installers or distributors when trouble happens to repair it.

2.Turn the power off and power on again, if the failure code recurs, please inform the franchiser.