Installation procedure Install indoor unit
Install the hoisting screw
Use M8 or M10 hoisting screw (4, prepare on site) (When the height of hoisting screw is more than 0.9m, you must use M10), their gaps refer to the dimension of air conditioner, according to the original structure and the following method to install.
wood structure
Put up the frame wood on the beam and mount the hoisting screws.
Frame wood
Hoisting screw
Beam
New cement panel
Use embedded parts and foot screw, etc to mount.
Iron
Foot screw (Knife type embedded part) (Louver type embedded part) (hoistingfootscrewforconnectionpipe)
Original cement panel
Use the in hole hinge, in hole plug or in hole screw.
Steel structure
Directly use angle steel or new angle steel for support.
Suspending bolt
Hoisting screw | Angle steel for support |
Suspending of indoor unit
Fix the cap of hoisting screw on and suspend them on the T groove of the hoisting part of the unit.
Use gradienter to keep the level degree of the unit within 5mm.
20