Installation procedureInstall indoor unit
*Notice
In order to normally drain water, the drain hose should be mated according to the installation manual. In order to avoid
Requirements:
The indoor side drain hose should be thermal insulated.
The parts connected with indoor unit should be thermal insulated. Improper thermal insulation may cause
The drain hose should be downwards slant (over 1/100) and there should be no
The horizontal length of the drain hose should be less than 20m. If the connection pipe is too long, the supporting frame should be set every 1.5~2m to prevent pipe from rise and fall.
For the centralized connection pipe, please perform work as the following Figure shown. Pay attention not to exerting external force to the connection part of the drain hose.
1.5m*2m | Supporting frame | As large as possible (about 10cm) | |
| |||
| Downward slant over 1/100 | VP30 |
Thermal insulation material user
Downward slant over 1/100
| wall |
| outside |
| Slant |
| Drain hose (user |
Material of connection pipe and thermal insulation | |
Material of connection pipe | Stiff PVC pipe VP 20mm (inside diameter) |
Material of thermal insulation | Foam polyethylene pipe, thickness over 10mm |
Confirm drainage
Perform test run to insure the condition of drainage, the connection part of the connection should not leak water. The confirmation must be performed even if install in winter.