Installation procedureInstall indoor unit

Confirm drainageInstallation procedureInstall indoor unit

*Notice

Manual background In order to normally drain water, the drain hose should be mated according to the installation manual. In order to avoid dew-forming, thermal insulation treatment should be done.Improper connection pipe may cause water enter indoor.

Requirements:

Manual background The indoor side drain hose should be thermal insulated.

The parts connected with indoor unit should be thermal insulated. Improper thermal insulation may cause dew-forming phenomenon.

Manual background The drain hose should be downwards slant (over 1/100) and there should be no S-shaped bend. Otherwise, abnormal sound may occur.

Manual background The horizontal length of the drain hose should be less than 20m. If the connection pipe is too long, the supporting frame should be set every 1.5~2m to prevent pipe from rise and fall.

Manual background For the centralized connection pipe, please perform work as the following Figure shown. Manual background Pay attention not to exerting external force to the connection part of the drain hose.

1.5m*2m

Supporting frame

As large as possible (about 10cm)

 

S-shaped bend

 

Downward slant over 1/100

VP30

Thermal insulation material user self-provided)

Downward slant over 1/100

 

wall

 

outside

 

Slant

 

Drain hose (user self-provided)

Material of connection pipe and thermal insulation

Material of connection pipe

Stiff PVC pipe VP 20mm (inside diameter)

Material of thermal insulation

Foam polyethylene pipe, thickness over 10mm

Confirm drainage

Perform test run to insure the condition of drainage, the connection part of the connection should not leak water. The confirmation must be performed even if install in winter.