Haier AU222XFERA, AU182XFERA installation manual Purging method to use vacuum pump

Models: AU182XFERA AU222XFERA

1 18
Download 18 pages 12.25 Kb
Page 12
Image 12
 Purging method: to use vacuum pump

Manual background Purging method: to use vacuum pump

1 .Detach the service portis cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way valves, connect the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump.

2 .Open the handle at low in gaugemanifold, operate vacuum pump. If the scale-moves of gause (low) reach vacuum condition in a moment, check 1 again.

3 .Vacuumize for over 15min. And check the level gauge which should read -0.1MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in the vacuum pump. Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, then return to the beginning of 3 .

4 .Open the valve rod for the 2-way valve to and an angle of anticlockwise 90 degree. After 6 seconds, close the 2- way valve and make the inspection of gas leakge.

5 .No gas leakage?

In case of gas leakage, tighten

 

parts of pipe connection. If

 

leakage stops, then proceed 6

 

steps.

6 .Detach the charge hose from the service port, open 2- way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly.

7 .To prevent the gas leakage, turn the service ports cap, the valve rodis cap for 2-way valve and 3-way's a little more than the point where the torque increases suddenly.

Liquid stop valve

 

Gas stop valve

2 way valve

 

3 way valve

Gauge maifold(R410A)

 

 

Vacuum pump(R410A)

Open

Close

2 way valve Manual backgroundManual background

Manual backgroundManual background 3 way valve 900 Manual backgroundManual backgroundManual background

Service port

Manual background 900 for 6 sec.

If it does not stop gas leakage, discharge whole refrigerants from the service port. After flaring work again and vacuumize, Manual background fill up prescribed refrigerant from the gas

cylinder.

2 way valveManual background

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background 6 3 way valve Manual backgroundManual backgroundManual background

6

2 way valve Manual background

3 way valve Manual backgroundManual backgroundManual background

Manual backgroundManual background Valve rod cap

Manual backgroundManual backgroundValve rod cap Manual backgroundManual background Service port cap

CAUTION:

If the refrigerant of the air conditioner leaks, it is necessary to make all the refrigerant out. Vacuumize first, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.

2 way valve

3 way valve

2 way valve

3 way valve

2 way valve

90o

10s

3 way valve

Manual background6.35mm To indoor unit A (1/4")

Manual background9.52mm (3/8")

Manual background6.35mm To indoor unit B (1/4")

Manual background 9.52mm (3/8")

6.35mm

To indoor unit C

(1/4")

 

Manual background9.52mm (3/8")

10

Page 12
Image 12
Haier AU222XFERA, AU182XFERA installation manual Purging method to use vacuum pump