Haier AU222XFERA, AU182XFERA installation manual Refrigerant piping work, Hose Drain elbow

Models: AU182XFERA AU222XFERA

1 18
Download 18 pages 12.25 Kb
Page 10
Image 10
 Refrigerant piping work

Hose Refrigerant piping work

1. Selection of pipe

Manual background To this unit, both liquid and gas pipes shall be insulated as they become low temperature in operation. Manual background Use optional parts for piping set or pipes covered with equivalent insulation material.

Liquid pipe

6.35mm ( 1/4'' ) x 0.8mm

 

 

Gas pipe

9.52mm ( 3/8'' ) x 0.8mm

 

 

2. Connection of pipe

Manual background Apply refrigerant oil on half union and flare nut.

Manual background To bend a pipe, give the roundness as large as possible not to crush the pipe.

Manual background Connecting the pipe of gas side firstly makes working easier.

Half union

 

 

Flare nut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Spanner

Torque wrench

Forced fastening without careful centering may damage the threads and cause a leakage of gas.

Pipe Diameter ( )

Fastening Torque

 

 

Liquid Side 6.35mm (1/4'')

18N.m

 

 

Gas Side 9.52mm (3/8'')

50N.m

 

 

3. Attaching Drain-Elbow

Manual background If the drain-elbow is used, please attach it as figure.

Hose

Drain elbow

8

Page 10
Image 10
Haier AU222XFERA, AU182XFERA installation manual Refrigerant piping work, Hose Drain elbow