3. Limitations values on the piping work .

L1 Limitations on the installation

3. Limitations values on the piping work .

L1

L2

L3

A

h

B

H +

H -

C

The piping length information, please refer the following table.

Item

Unit

Descriptions

Standard

Maximum

A, B, Cliquid pipe

mm

Size of the liquid side connection pipe

6.35

/

A, B, C Gas pipe

mm

Size of the gas side connection pipe

9.52

/

 

 

 

 

 

 

L1

(one way)

m

Pipe length when the compressor connects with two indoor units

*10

*25

 

 

 

 

 

 

L2

(one way)

m

Pipe length when the compressor connects with two indoor units

*10

*25

 

 

 

 

 

 

L3

(one way)

m

Pipe length when the compressor connects only one indoor unit

*10

*25

 

 

 

 

 

L1+L2+L3

m

Total liquid piping length

*30

*45

 

 

 

 

 

 

h

 

m

Drop between every two indoor units

*1

*5

 

 

 

 

 

 

H +

 

m

Drop between the outdoor unit and the indoor unit

*5

*15

 

 

 

 

 

 

H -

 

m

Drop between the outdoor unit and the indoor unit

*5

*10

 

 

 

 

 

 

7