2Selection of installation place
Installation space

3Preparation for the installationManual background Installation Procedure

1Before installation <Don't discard any accessories until completed>

Determine the way to carry unit to installation place.

Don't remove packing until unit reaches installation place.

If unpacking is unavoidable, protect unit properly.

2Selection of installation place

(1) Installation place shall meet the following and agreed by customers:

Place where proper air flow can be ensured.

No block to air flow.

Water drainage is smooth.

Place strong enough to support unit .

Place where inclination is not evident on ceiling.

Enough space for maintenance.

Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.)

Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radio. This is helpful to avoid picture disturbance and noise. (Even if 1 m is kept, noise can still appear if radio wave is strong)

(2) Ceiling height

Indoor unit can be installed on ceiling of 2.5-3m in height. (Refer to Field setting and Installation Manual of ornament panel.)

(3)Install suspending bolt. Check if the installation place is strong enough to hold weight. Take necessary measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern for place which need be reinforced)

Air outlet

1500 Over

2500 Over

 

310

Air inlet

Air outlet

 

1500 Over

3Preparation for the installation

(1) Position of ceiling opening between unit and suspending bolt.

Indoor unit 570mm

Ceiling opening 650mm

Ornament panel 700mm

Distance between

 

 

suspending bolts 535mm

 

 

Indoor unit 570mm

 

 

Ceiling opening 650mm

 

 

Ornament panel 700mm

 

 

Overlap between ceiling and ornament panel shall be 25mm

Ceiling

Ornament panel

 

Suspending bolts

150mm

320mm

60mm

 