When Trouble Happens

Trouble display

Reason

The phenomenon of indicator light on indoor remote receiver

 

 

 

Room temp. sensor malfunction

"Run" light flashes once

Indoor coil temp. sensor malfunction

"Run" light flashes twice

 

Drainage system malfuntion

"Run" light flashes ten times

 

Low pressure protection

"Run"light flashes sixteen times

The exterior alarm signal input

"Run" light flashes eleven times

The defrosting sensor malfunction

"Run" light flashes four times(Heat pump model)

 

 

 

The indoor coil temperature is higher

 

 

than room temperature when cooling

"Run" light flashes thirteen times

or the former is lower than the later

 

 

when heating

 

 

 

 

 

Change-over switch

BM1

(1) OFF

(2)OFF

 

 

 

 

(1) OFF

(2)OFF (Cooling only unit)

 

 

 

BM2

(1) OFF

(2)ON (Heat pump model)

 

 

(3) OFF/ON

Heat pump model/Cooling only unit

 

 

 

 

 

(4) ON/OFF

Defrost sensor/No defrost sensor

 

 

 

BM3

 

OFF

BM4

 

OFF