Room Sensor and Rear Shield Installation | 12 | |
|
|
|
Room Sensor Installation | Rear Shields |
|
| 5/16" Hex Head | |
5/16" Hex Head | Screws (2 on | |
each side) | ||
Screws (2 on | ||
| ||
each side) |
|
Fig. 19
The room sensor is a small temperature sen- sor on the end of a 60" gray wire. This sensor is installed much like a standard wall thermostat. Be- cause it is so small, it can be hidden along the trim of a doorway or even up the leg of a coffee table. There is a remote room sensor port on the rear of the unit for easy external connection. Use standard
NOTE: Distances of more than 25 feet from the unit or in another room are not recommended. The room sensor is essential for the Accentra's ex- cellent efficiency.
It is recommended that the roomsensor be installed, even if only installed on the rear of the unit as a return air sensor. There is an intake screen on the bottom of the rear sheetmetal enclosure. This is an ideal place to tyrap the sensor head to sense return air temperature.
Fig. 20
The rear isolated shields are split in the middle for easy removal. Each shield has two 5/16" hex head screws that only need to be loosened (NOT REMOVED) to allow the shield to slide away from the unit. NOTE: It is not recommended that the unit be operated with the shields removed, due to the hot and moving parts which they protect.
REMINDERS
Hopper Lid Foam
Gaskets
Hopper lip
Fig. 21
Do not allow pellets or sawdust to build up on the hopper lip.
Inspect the hopper lid gasket for damage. A good hopper lid seal is very important for proper operation.