VENTING

VENTING

Use Only Approved Venting

The Clarity Direct Vent Gas Heater has been tested and is listed for installation with Simpson Duravent GS vent- ing components. The Simpson Duravent GS warranty will be voided, and serious fire, health, or other safety hazards may result from any of the following actions:

Installation of any damaged Duravent GS component.

Unauthorized modification of the Duravent GS System.

Installation of any component part not manufactured or

approved by Simpson Duravent.

Installation other than as instructed by Simpson Duravent and the appliance manufacturer.

Consult your local building codes before beginning the installation, and follow the manufacturer's instructions ex- actly. The following Simpson Duravent GS 4" X 6 5/8" vent- ing components are approved for use with the Clarity Di- rect Vent Gas Heater.

SIMPSON DURA-VENTCOMPONENT NO.

Basic Termination Kit

970

Horizontal Termination Kit A

971

VerticalTermination Kit A

973

Horizontal Square Termination Cap

984

VerticalTermination Cap

983

Snorkel Termination Cap, 36" Vertical Rise

981

Snorkel Termination Cap, 14" Vertical Rise

982

Vinyl Siding Standoff

950

Wall Thimble

942

Round Ceiling Support/Wall Thimble Cover

940

Cathedral Ceiling Support Box

941

Storm Collar

953

Firestop Spacer

963

Adjustable RoofFlashing, 0/12-6/12 pitch

943

Steep Roof Flashing, 7/12-12/12 pitch

943S

Wall Strap

988

Designer Series Trim Kits

3951,3952,3953,

 

3960,3961,3962

High WindVertical Termination Cap

991

Low Profile Termination Cap

980

DIRECT VENT PIPE LENGTHS

 

 

DURA-VENTCOMPONENTNO.

 

GALVANIZED

BLACK

6" length

NA

908B

9" length

NA

907B

12" length

906

906B

24" length

904

904B

36" length

903

903B

48" length

902

902B

11-14 5/8" Adjustable

-

911B

45° Elbow

945

945B

90° Elbow

990

990B

The Clarity Direct Vent should be installed with no more than 12 joints and 2 elbows. The elbows may be either 45° or 90°.

The Clarity Direct Vent must not be connected to a chim- ney flue serving any other appliance.

WARNING: The flow of ventilation air must not be obstructed.

Horizontaland Vertical Venting Requirements

The maximum horizontal run allowed for the Clarity Di- rect Vent is 10 feet. The maximum vertical rise and maxi- mum total vent length is 30 feet. The horizontal and vertical lengths of venting must fall within the shaded portion of the chart below:

Restrictor plates supplied by Harman (Part No. G218) may be added in straight vertical installa- tions only. For each 10' of vertical rise above the first 10', one restrictor plate may be added. No more than two restrictor plates may be used.

For venting systems that utilize one or two el- bows (either 45° or 90°), restrictor plates

should not be used.

For the Clarity Direct Vent, the vent/ air intake termination clearances above the high side of an angled roof are as follows:

Vertical (feet)rise

Horizontal run (feet)

 

Roof Pitch

Feet

Meters

Flat to 6/12

1

0.3

7/12 to 9/12

2

0.6

10/12 to 12/12

4

1.2

13/12 to 16/12

6

1.8

17/12 to 21/12

8

2.4