Requirements for Terminating the Venting

VENTING

Requirements for Terminating the Venting

WARNING: Venting terminals must not be recessed into a wall or siding.

In addition, the following must be observed:

A. The clearance above grade, or a veranda, porch, deck or balcony must be a minimum of 12" (30 cm).1

B. The clearance to a window or door that may be opened must be a minimum of 12" (30 cm).1

C. A 12" (30 cm) clearance to a permanently closed win- dow is recommended to prevent condensation on the win- dow.

D. The vertical clearance to a ventilated soffit located above the terminal within a horizontal distance of 2 feet (60 cm) from the center-line of the terminal must be a mini- mum of 18" (46 cm).

E. The clearance to an unventilated soffit must be a mini- mum of 12" (30 cm).

F. The clearance to an outside corner is 9" (23 cm). G. The clearance to an inside corner is 12" (30 cm).

H.A vent must not be installed within 3 feet (90 cm) above a meter/regulator assembly when measured from the horizontal center-line of the regulator.1

I.The clearance to service regulator vent outlet must be a minimum of 6 feet (1.8 m).1

J.The clearance to a non-mechanical air supply inlet to the building or the combustion air inlet to any other appli- ance must be a minimum of 12 feet (30 cm).1

K.The clearance to a mechanical air supply inlet must be a minimum of 6 feet (1.8 m).1

L.The clearance above a paved sidewalk or a paved driveway located on public property must be a minimum of 7 feet (2.1 m).1,2

M.The clearance under a veranda, porch, deck or bal- cony must be a minimum of 12 inches (30 cm).1,3

1As specified in CAN 1 B1-149 Installation Codes (currend edition). Note: local codes or regulations may require dif- ferent clearances.

2A vent shall not terminate directly above a side-walk or paved driveway which is located between two single fam- ily dwellings and serves both dwellings.

3Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath the floor.

Connecting To An Existing Chimney

The Clarity may be connected to an existing ma-

sonry chimney by using aSimpson Dura-Vent con-

version kit #934.

With this kit and a 4" flex linner in the chimney the

flue gases exit through the 4" linner and the outside

air comes down the chimney in the space between

the chimney and the linner. This method allows you

to install the Clarity your chimney and still get the

added efficiency provided by direct venting.

The use of an existing chimney as an

air intake is not covered under the ANSI Z21.50-1996. CGA 2.22-M96 test methods and the resulting ITS/WHI product certfication: The code AuthorityHaving Juris- diction must be consulted prior to proceeding.

D

WARNING: Venting terminals must not be recessed into a wall or siding.In addition, the following must be observed:VConnecting To An Existing Chimneyversion kit #934. E

Manual backgroundManual backgroundB

L V

F

C

VFixed

Closed

V

Op enab le

 

BManual backgroundManual background

I ns ide

Corner

Det ail

G

V

A

B

V

 

B

V

Openable

Fixed

 

 

 

Closed

 

 

V J

B

B

A

 

 

 

A

 

H

M

V

K

A

V

= Vent terminal

A = Air supply inlet

6

 

 

= Area where terminal is not permitted

Page 6
Image 6
Harman Stove Company 929 DV Connecting To An Existing Chimney, Requirements for Terminating the Venting, version kit #934