| P35i Fireplace Insert |
|
|
B. Clearances To Combustibles - | D. Minimum Opening for Masonry |
Masonry or Manufactured Fireplace | and Manufactured Fireplaces |
The clearances specified are for your safety! These clearances may only be reduced by means approved by the regulatory authority.
| Mantel | |
| Face Trim | |
Side Wall | B | |
D | ||
| ||
A | C | |
| ||
F | E |
| Location | Inches | Millimeters |
|
|
|
|
A | Insert to combustible sidewall | 13 | 330 |
|
|
|
|
B | Surround top to face trim | 0 | 0 |
C | Surround side to face trim | 1 | 25.4 |
|
|
|
|
D | Insert top to (max) 12" mantel | 12 | 305 |
C. Floor Protection Requirements
| Location | Inches | Millimeters |
|
|
|
|
E | Window opening to front | 6 | 152 |
|
|
|
|
F | Window opening to side | 6 | 152 |
Hearth extension must be of a
Minimum Size Hearth Extension is 16" Deep By 32" Wide.
I |
H |
G |
| Location | Inches | Millimeters |
|
|
|
|
G | Minimum Width | 24 | 609 |
|
|
|
|
H | Minimum Depth | 14.5 | 368 |
I | Minimum Height | 23½ | 597 |
I | Minimum Height | 19½ | 495 |
E. Mantel Projections
J |
K |
The Maximum mantel depth (J) is 12 inches (305 mm) with a minimum vertical height (K) of 12 inches (305 mm).
10 Pellets or Corn/Pellet Mixture Only | Save These Instructions |