CHIMNEY REQUIREMENTS

R

4100-I ACT WOOD INSERT

CHIMNEY REQUIREMENTS

A chimney must be the required height above the roof or other obstruction for safety and for proper draft oper- ation. The requirement is that the chimney must be at least 3 feet (91cm) higher than the highest point where it passes through the roof, and at least 2 feet (61cm) higher than the highest part of the roof or structure that is within10 feet (305cm) of the chimney, measured hori- zontally. Refer to Figure 8C.

OVALIZING ROUND STAINLESS STEEL

LINERS

Ovalizing round stainless steel liners to accommodate the liner passing through the damper region of a fire- place is an allowable and acceptable practice.

Ensure that the ovalization is minimized to the extent required to fit through the damper.

Figure 8A

Firestopping

Figure 8C

Non-Combustible

Firestopping

Material

2 inch (51mm)

Floor

(second Story)

Floor

Ceiling

Caulk

Minimum 1 inch (25mm) clearance from exterior chimney to sheathing

CHIMNEY HEIGHT

At least  ft

(91cm)

10 ft

(05cm)

At least 2 ft

(61cm)

Figure 8B

Figure 8D

Minimum 2 inch (51mm) clearance from combustible material

and insulation

ceiling

Non-combustible fire stopping material

CHIMNEY TOp VIEW

1/2" (12.7mm) airspace

FLUE

5/8" (16mm) Fireclay Flue Liner

Chimney Wall

4" (102mm)