E. Install the Attic Insulation Shield

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tabs

An insulation shield must be installed when there is a pos-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sibility of insulation coming into contact with the factory built

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

chimney system.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Bend the tabs at the top of the attic insulation shield inward.

24

 

in.

 

 

 

 

 

 

 

(423 mm) Attic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This will help keep the chimney section centered in the

(610

 

mm)

 

 

 

 

 

 

 

 

 

Insulation

Insulation

 

 

 

 

 

 

 

 

 

 

 

 

 

Shield

shield.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling Firestop

• Position the shield over the vertical chimney section where

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

it penetrates a ceiling firestop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slide the shield down until it rests on the ceiling firestop.

The ceiling firestop will support the insulation shield. See

 

13 in.

 

 

Figures 5.4 and 5.5.

 

 

 

 

 

(330 mm)

 

 

WARNING

 

 

Chimney

 

Figure 5.4 Install Attic Insulation Shield Above the Ceiling

Fire Risk

 

 

 

 

• DO NOT pack insulation or other

 

 

 

 

combustibles: between ceiling firestops;

 

 

 

 

between chimney and attic insulation

17 in.

 

Tabs

 

shield.

 

Attic

 

 

• ALWAYS maintain specified clearances

(423 mm)

 

Insulation

around chimney and ceiling firestops.

Insulation

24 in.

 

Shield

• Install ceiling firestops as specified.

 

 

Failure to keep insulation or other material

(610 mm)

 

 

 

 

 

 

away from chimney pipe may cause fire.

 

 

 

 

F. Double-check the Chimney Assembly

 

 

 

 

Continue assembling the chimney sections up through the

13 in.

 

 

ceiling firestops as needed. While doing so, be aware of the

 

 

(330 mm)

Ceiling Firestop

height and unsupported chimney length limitations given un-

 

Chimney

der Section 5.A. Chimney Requirements.

 

 

 

 

 

 

 

Check each section by pulling up slightly from the top to en-

Figure 5.5 Install Attic Insulation Shield Below the Ceiling

sure proper engagement before installing the succeeding

 

 

 

 

sections. If they have been connected correctly, they will not

 

 

 

 

disengage when tested.

 

 

 

 

G. Secure the Chimney

 

 

When offsets and returns are joined to straight pipe sections,

 

 

they must be locked into position with the screws provided*

 

 

(outer only), using the predrilled holes. To prevent gravity

 

Ceiling

from pulling the chimney sections apart, the returns and the

 

Straps

Firestop

chimney stabilizers have hanger straps for securing these

 

parts to joists or rafters. See Figure 5.6.

 

Joint

* or equivalent #6 or #8 sheet metal screw no longer than

 

 

Band

3/4 in. (19 mm).

 

Optional

(Optional)

 

Additional

 

WARNING

Support

 

 

 

Fire Risk

Secure offsets with screws (not to exceed

3/4 in./19 mm in length).

Figure 5.6 Secure the Chimney

Secure returns with strapping.

Straight chimney sections may be secured with screws (not to exceed 3/4 in./19 mm in length) at the joints.

Keep chimney sections from separating or twisting.

Outdoor Lifestyles by Hearth & Home Technologies Inc. • Montana US-CAN4039-156 Rev K • 7/11

17

Page 17
Image 17
Hearth and Home Technologies 36 Install the Attic Insulation Shield, Double-check the Chimney Assembly, Secure the Chimney