6Complete the Enclosure

A. Chimney Termination

Chimney Termination Requirements (See Figure 6.1)

Must have a cap approved and listed for this fireplace system

Must not be located where it will become plugged by snow or other material

Must terminate at least 3 ft (914 mm) above the roof and at least 2 ft (610 mm) above any portion of the roof within 10 ft (3.05 m)

Must be located away from trees or other structures

Slanted Roofs

Chimney must extend 3 ft (.9 m) above the roof

Flat Roofs

Chimney must extend 3 ft (.9 m) above the roof

Chimney must extend 2 ft (.6 m) above any portion of the roof or adjacent structures within

10 ft (3 m) of the chimney

Chimney must extend 2 ft (.6 m) above any portion of the roof or adjacent structures within

10 ft (3 m) of the chimney

Multiple Chimney Locations

Gas, Wood or Fuel Oil

Termination Cap

A

B

6 in. (minimum) up to 20 in.

18 in. minimum

152 mm/508 mm

457 mm

20 in. and over

0 in. minimum

B

Gas

Termination

Cap **

A *

Wood Minimum

(See

illustration

above)

Perpendicular Wall

*If using decorative cap cover(s), this distance may need to be increased. Refer to the installation instructions supplied with the decorative cap cover.

** In a staggered installation with both gas and wood terminations, the wood termination cap must be higher than the gas termination cap.

Figure 6.1 Multiple Chimneys

18 Outdoor Lifestyles by Hearth & Home Technologies Inc. • Montana US-CAN4039-156 Rev K 7/11

Page 18
Image 18
Hearth and Home Technologies 42, 36 owner manual Complete the Enclosure, Chimney Termination