Modbus TCP Remote I/O Communication Module
DVP28SV
RUN
STOP
Ethernet |
|
|
TS8 0 | 16SP | DA4 0 |
DVP- | ||
COM2 |
|
|
DI/DO |
|
PC |
CT40 | TP4 0 | 02DA |
DVP- |
AI/AO
4 | Word Devices & Bit Devices in |
|
| |||
4.1 | Basic Registers (BR) |
|
|
| ||
|
|
|
|
|
|
|
| BR# | Attribute | Content | Explanation | Default | Latched |
| 0 | R | Model name | Set up by the system; read only. The model code of | H’0600 | YES |
| ||||||
|
|
|
|
|
| |
| 1 | R | Firmware version | Displaying the current firmware verision in hex, e.g. V1.2 is |
| YES |
| indicated as high byte = 0x01 and low byte = 0x20. |
| ||||
|
|
|
|
|
| |
|
|
|
| Displaying the data in decimal form. 10,000s digit and 1,000s |
|
|
|
|
|
| digit are for “month”; 100s digit and 10s digit are for “day”. For |
|
|
| 2 | R | Release date of the | 1s digit: 0 = morning; 1 = afternoon. |
| YES |
| version |
|
| |||
|
|
| Example: 12191 indicates the version released in the afternoon |
|
| |
|
|
|
|
|
| |
|
|
|
| of December 19. |
|
|
| 3 | R/W | Start/Stop PLC |
|
| NO |
| function |
|
| |||
|
|
|
|
|
| |
| 4 |
| Reserved | . |
| NO |
|
|
|
|
|
|
|
|
|
| COM2 |
|
| |
| 5 | R/W | communication | H’0368 | YES | |
| baud rate setting and communication format setting. | |||||
|
|
| settings |
|
| |
|
|
|
|
|
| |
| 6 | R/W | Address | For setting up the station address | K’1 | YES |
|
|
|
|
|
|
|
| 7 | R | Number of DI points | Range: 0 ~ 256 |
| NO |
|
|
|
|
|
|
|
| 8 | R | Number of DO points | Range: 0 ~ 256 |
| NO |
|
|
|
|
|
|
|
| 9 | R | Error code | Displaying the errors. Please refer to the table of error codes. |
| NO |
|
|
|
|
|
|
|
| 10 |
| Reserved |
|
| NO |
|
|
|
|
|
|
|
| 11 | R/W | Communication | For setting up the communication | K’5000 | YES |
| TCP mode. | |||||
|
|
|
|
| ||
| 12 | R/W | Communication delay | For setting up the minimum interval time between every | K’0 | YES |
| time | communication datum. | ||||
|
|
|
|
| ||
| 13 | R/W | TCP connection idle | For setting up idle time for TCP communication. Unit: second | K’30 | YES |
| time | |||||
|
|
|
|
|
| |
| 14 ~ 22 |
| Reserved |
|
| NO |
|
|
|
|
|
|
|
| 23 | R | Number of analog I/O | Max. 8 |
| NO |
|
|
| modules |
|
|
|
8 |