3. Low Ice Production

3. Low Ice Production

Low Ice Production - Possible Cause

 

Long Harvest Cycle

 

 

1. Evaporator

a) Scaled up, dirty.

 

 

2. Ice Chute

a) Out of position.

 

b) Damaged.

 

 

3. Refrigerant Charge

a) Low.

 

 

4. Control Board

a) Thermistor connection loose.

See "III.B. Settings and

 

b) Harvest control moved from factory setting.

Adjustments."

c) Defective.

 

 

 

5. Thermistor

a) Loose, disconnected, or defective.

See "II.E. Thermistor Check"

 

 

 

6. Hot Gas Valve

a) Erratic or closed.

 

 

7. Inlet Water Valve

a) Screen or orifice clogged.

8. Compressor

a) Inefficient or off.

 

 

 

Long Freeze Cycle

 

 

1. Evaporator

a) Scaled up, dirty.

 

 

2. Inlet Water Valve

a) Leaking by.

3. Hot Gas Valve

a) Erratic or open.

4. Condenser

a) Clogged.

 

 

5. Thermistor

a) Loose, disconnected, or defective.

See "II.E. Thermistor Check"

 

 

 

6. Control Board

a) Freeze control set too long.

See "III.B. Settings and

 

b) Defective.

Adjustments."

 

 

 

7. Refrigerant Charge

a) Low.

8. Compressor

a) Inefficient or off.

 

 

9. Pump Motor

a) RPM too slow.

 

 