C. Bin Control Check

7)Shutdown. When the appliance is running, hold ice in contact with the thermostatic bulb. BC switch opens within 10 sec., shutting down the appliance. BC is factory set, and generally no adjustment is required. However, adjustment may be needed in some conditions, particularly at higher altitude locations.

Legend: BC–bin control; CB–control board; Comp–compressor; FM–fan motor; FT–freeze timer; FTT–freeze termination timer; HGV–hot gas valve; HT–harvest timer; PM–pump motor; WV–inlet water valve; WVT–inlet water valve timer

C. Bin Control Check

BC shuts down the icemaker within 10 sec. when ice contacts the thermostatic bulb, regardless of the cycle at activation.

NOTICE

When the ambient temperature is below 45°F (7°C), BC opens and shuts down the appliance even if the ice storage bin is empty.

To check BC, follow the steps below.

1)Move the control switch to the "OFF" position.

2)Unplug the appliance.

3)Remove the control box cover. Loosen the control box from the base and slide it out for easy access. Next, clear any ice away from BC bulb.

4)Use the wiring diagram to locate the 2 wires supplied to BC. Disconnect BC wires.

5)Hold your hand around the bulb to warm it up.

6)Check for continuity across BC wires. If closed, continue to step 7. If open, replace BC.

7)With the multimeter test leads still in place, hold ice in contact with BC bulb. BC should open within 10 sec. If not, BC must be adjusted. Installations at higher altitude locations are more likely to require adjustment. If BC will not shut down the appliance even after being adjusted, replace BC.

Legend: BC–bin control