Modbus TCP Remote I/O Communication Module RTU-EN01

„Environment

Noise immunity

Operation

Storage

Shock/vibration immunity

Certificates

„Electrical specification

Power supply voltage

Power fuse capacity

Power consumption

Insulation voltage

Weight

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge

EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV,

Communication I/O: ±2KV

RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 100MHz, 10V/m. 1.4GHz ~ 2.0GHz, 10V/m

Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150kHz ~ 80MHz, 3V/m

Surge Test (Biwave IEC61132-2, IEC61000-4-5): Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM

0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity), pollution degree 2 -25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity)

International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

24VDC (-15% ~ 20%) (with DC input polarity reverse protection) 1.85A/30VDC, Polyswitch

2W

500VDC

116g

2 Product Profile & Outline

2.1 Dimension

37.460

LAN

RUN

POWER

RUN

BAT.LOW

STOP

RTU-EN01

RS-485

RS-232

Unit: mm

4

DVP-PLC Operation Manual

Page 6
Image 6
Delta Electronics RTU-EN01 operation manual Dimension 37.460