Modbus TCP Remote I/O Communication Module
R# | Attribute | Content | Explanation | Default | Latched |
6 | R/W | RTC 6 | OFF | NO | |
|
|
|
|
|
|
7 | R/W | RTC 7 | OFF | NO | |
|
|
|
|
|
|
8 | R/W | RTC 8 | OFF | NO | |
|
|
|
|
|
|
9 | R/W | RTC 9 | OFF | NO | |
|
|
|
|
|
|
10 | R/W | RTC 10 | OFF | NO | |
|
|
|
|
|
|
11 | R/W | RTC 11 | OFF | NO | |
|
|
|
|
|
|
12 | R/W | RTC 12 | OFF | NO | |
|
|
|
|
|
|
13 | R/W | RTC 13 | OFF | NO | |
|
|
|
|
|
|
14 | R/W | RTC 14 | OFF | NO | |
|
|
|
|
|
|
15 | R/W | RTC 15 | OFF | NO | |
|
|
|
|
|
|
Symbol “R” refers to ready only; “R/W” refers to read and write.
R#0: RTC 0
Explanations:
When the RTC function is enabled, and the assigned trigger condition is true,
R#1 ~ #15: RTC 1 ~ 15
Explanations:
Please refer to R#0.
5 | Modbus Communication |
|
| |||
5.1 | Function Codes Supported |
|
| |||
|
|
|
|
|
|
|
|
| Function code | Explanation |
| Devices supported |
|
|
| 0x02 | Read digital input point |
| RX, RY, T, R, C |
|
|
|
|
|
|
|
|
|
| 0x03 | Read register |
| BR, T, C, RCR |
|
|
|
|
|
|
|
|
|
| 0x05 | Write single bit device |
| RY, T, R, C |
|
|
|
|
|
|
|
|
|
| 0x06 | Write single register |
| BR, T, C, RCR |
|
|
|
|
|
|
|
|
|
| 0x0F | Write multiple bit devices |
| RY, T, R, C |
|
|
|
|
|
|
|
|
|
| 0x10 | Write multiple registers |
| BR, T, C, RCR |
|
|
|
|
|
|
|
|
|
| 0x17 | Read/write multiple registers |
| BR, T, C, RCR |
|
|
|
|
|
|
|
|
5.2 | Exception Codes Supported |
|
| |||
|
|
|
|
|
| |
|
| Exception code | Explanation |
|
| |
|
| 0x01 | Illegal function |
|
| |
|
|
|
|
|
| |
|
| 0x02 | Illegal data address |
|
| |
|
|
|
|
|
| |
|
| 0x03 | Illegal data value |
|
| |
|
|
|
|
|
| |
|
| 0x04 | Slave device failure |
|
| |
|
|
|
|
|
| |
|
| 0x0b | Gateway target device failed to respond. |
|
| |
|
|
|
|
|
|
|
15 |