Modbus TCP Remote I/O Communication Module RTU-EN01

BR#5: COM2 Communication Settings

Explanations:

b0 ~ b3

Content

Interface

 

 

Explanation

 

 

 

 

 

 

 

 

 

 

Data

Baud rate

Data

Baud rate

Data

Baud rate

 

(bps)

(bps)

(bps)

 

 

 

 

 

 

 

 

 

 

 

COM2

0x1

110

0x6

2,400

0xB

57,600

 

 

 

 

 

 

0x2

150

0x7

4,800

0xC

115,200

RS-485

 

 

 

 

 

 

0x3

300

0x8

9,600

 

 

 

 

 

 

 

 

 

 

 

 

 

0x4

600

0x9

19,200

 

 

 

 

 

 

 

 

 

 

0x5

1,200

0xA

38,400

 

 

 

 

 

 

 

 

 

b4 ~ b7

 

 

 

 

b7

 

 

 

 

b6 ~ b5

 

 

 

b4

 

 

 

 

Stop bit

 

 

 

Parity bit

 

 

 

Data bit

 

 

 

 

 

 

 

 

00 : None parity bit

 

 

 

 

Explanation

 

0: 1 Stop bit

 

 

 

 

0 : 7 Data bits

 

 

 

 

 

 

01 : Odd parity bit

 

 

 

 

 

1: 2 Stop bits

 

 

 

1 : 8 Data bits

 

 

 

 

 

 

11 : Even parity bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0000 (0)

7-N-1

0011 (3)

 

8-O-1

1000 (8)

 

7-N-2

 

1011 (B)

8-O-2

 

Content

 

 

 

 

 

 

 

 

 

 

 

 

0001 (1)

8-N-1

0110 (6)

 

7-E-1

1001 (9)

 

8-N-2

 

1110 (E)

7-E-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0010 (2)

7-O-1

0111 (7)

 

8-E-1

1010 (A)

 

7-O-2

 

1111 (F)

8-E-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b8 ~ b15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Content

0x02

0x03

Explanation

Modbus RTU Master

Modbus ASCII Master

BR#6: Address

Explanations

For filling in or reading the Modbus address. The address will be displayed in the message display after being set up. Range: 1 ~ 247.

BR#7: Number of DI Points

Explanations

Read the number of digital input points from BR#7. Range: 0 ~ 256. Max. I/O points: 256.

BR#8: Number of DO Points

Explanations

Read the number of digital output points from BR#8. Range: 0 ~ 256. Max. I/O points: 256.

BR#9: Error Code

Explanations:

Error code = 0 refers to no error occurring.

Code

Indication

How to correct

10

DVP-PLC Operation Manual

Page 12
Image 12
Delta Electronics RTU-EN01 BR#5 COM2 Communication Settings, BR#6 Address, BR#7 Number of DI Points, BR#9 Error Code