Modbus TCP Remote I/O Communication Module RTU-EN01

1.Enable:

Decide whether to trigger the RTC in this column.

2.Cyclic:

Decide to trigger the RTC only once, or trigger it on a daily, weekly or monthly basis.

3.Output auto-reset:

After the RTC is triggered, decide whether to retain the output for a period of time and reset the RTC automatically. R (Coil) will be OFF when the time for reset is reached.

4.Auto-reset time, Unit:

If you select to auto-reset the RTC, the bit device in RTC will retain the output for a period of time. Range: 1s ~ 24hr.

Range for second as unit: 1 ~ 32,767

Range for minute as unit: 1 ~ 3,600

Range for hour as unit: 1 ~ 24

5.Year, Month, Day, Hour, Minute, Second, Week:

The time to trigger the RTC. If you would like to trigger it only once, only Year, Month, Day, Hour, Minute and Second need to be set. If you would like to trigger on a daily basis, only Hour, Minute and Second need to be set. If you would like the RTC to be triggered on a weekly basis, you only need to set up Week, Hour, Minute and Second. If the RTC is triggered monthly, set up only Day, Hour, Minute and Second.

6.11Analog Input/Output Modules

RTU-EN01 offers control registers (CR) for analog I/O modules and is built-in with mapping tables of CR for read/write. The user can check the CR to be read/written and use Delta’s communication module DVPEN01-SL to map the CR directly to D registers in DVP-SV series PLC and read/write the D register through PLC program, controlling the analog I/O module connected to RTU-EN01. RTU-EN01 supports maximum 64 data reading/writing.

fThis function works with DVPEN01-SL of firmware V2.0 or versions above.

„Analog I/O modules

DVP-PLC Operation Manual

27

Page 29
Image 29
Delta Electronics RTU-EN01 operation manual Analog Input/Output Modules