Modbus TCP Remote I/O Communication Module RTU-EN01

3.Switch to “IF-THEN” page. Check the “Enable” box and select “RT0 On” in the IF column and “RY 0 Set” in the THEN column. Press “Add” to add the settings to the table below.

4.Check “Enable” and select “RT0 Off” in the IF column and “RY 0 Reset” in the THEN column. Press “Add" to add the settings to the table bellow and click on “OK” to save the settings into RTU-EN01.

7.19 Virtual COM

 

The virtual COM converts the data sent to RS-232 port into Ethernet. Virtual COM only

Application

connects to software supporting serial ports, e.g. Delta WPLSoft, VFDSoft, ASDASoft. See

the examples below for how to connect VFD-E series AC motor drive to VFDSoft through by

 

 

virtual COM.

 

 

 

 

(1)

Select user-defined protocol and set the communication parameters for serial

Steps

 

master/slave to the same as the parameters in VFD-E.

(2)

Set up virtual COM.

 

(3)Open Delta VFDSoft, set up the communication format and establish the connection.

1.Setting up virtual COM

„Select Virtual COM for COM2 mode (RS-485) and set up the same communication parameters as those in VFD-E.

46

DVP-PLC Operation Manual

Page 48
Image 48
Delta Electronics RTU-EN01 operation manual Virtual COM