5100-I WOOD INSERT

CLEARANCES TO COMBUSTIBLES

United States and Canada

 

 

Mantel

 

SideWall

B

Fascia or Trim

 

C

 

 

 

 

 

A

Insert

D

 

 

 

 

 

 

F

E

 

Hearth Extension

In Canada a full length 6” (152mm) S635 flue liner required as per ULC S628.

NOTE: When installling into a masonry fireplace, the fire- place must be built to UBC Chapter 37 standards. Do not remove brick or mortar from masonry fireplace to accomo- date insert. The permanent metal warning plate provided must be attached to the back of the fireplace stating the fire- place may have been altered to accomodate the insert and must be returned to original condition for use as a conven- tional fireplace.

 

A

B

C

D

E

F

 

 

INSTALLATION: Masonry, Heat Circulating and *Zero Clearance

 

 

 

 

12" (305)

40" (1016)

35" (889)

7" (178)

16" (406)

8"(200)

 

 

 

 

 

 

18" (457) Canada

 

 

 

 

 

 

 

 

 

With 5" Mantel Deflector, Part No. 831-1520

 

 

 

 

 

 

 

 

 

 

 

 

 

12" (305)

29" (737)

20" (889)

7" (178)

16" (406)

8"(200)

 

 

 

 

 

 

18" (457) Canada

 

 

 

 

 

 

 

 

 

With 8" Mantel Deflector, Part No. 831-1530

 

 

 

 

 

 

 

 

 

 

 

 

 

12" (305)

23" (585)

16" (406)

7" (178)

16" (406)

8"(200)

 

 

 

 

 

 

18" (457) Canada

 

 

*Zero Clearance in USA Only.

THERMAL PROTECTION USA & CANADA

Thermal protection must be 1 inch (25mm) minimum thickness (“k” value = 0.84) or equivalent material. See Alternate Floor Protection Work Sheet on page 7.

SERIAL NUMBER LABEL LOCATION:

ON RIGHT SIDE OF INSERT AS YOU FACE THE APPLIANCE