Hearth and Home Technologies 5100-I installation instructions Installation Options

Models: 5100-I

1 24
Download 24 pages 61.76 Kb
Page 10
Image 10

R

5100-I WOOD INSERT

INSTALLATION OPTIONS

Refer to: Clearances to Combustibles on page 5, Canadian Installation requirements on page 12,

Hearth Requirements on page 5 and Zero Clearance Adjustable Support Kit on page 16.

MASONRY FIREPLACE

USING DIRECT-CONNECT METHOD

The Quadra-Fire 5100-I Insert conforms with the UL Stan- dard for Safety 1482 and ULC S628 (Canada) in all respects, and is approved to UL & ULC safety standards for installa- tion and use within a fireplace with a masonry chimney in accordance with NFPA No. 211, with or without a direct flue collar connection. A starter pipe is required to reach to the bottom of the existing flue.

1.Secure the fireplace damper in the open position. If this cannot be accomplished, it will be necessary to remove the damper.

2.Seal either the damper area around the chimney liner with a high temperature sealant or the fireplace front with fiberglass batting.

3.The chimney should be examined for cracks, loose mortar, and other signs of deterioration and blockage. The insert should not be installed until it is determined that the chim- ney is safe for use. Since an oversized flue contributes to the accumulation of creosote, the size of the flue should be checked to determine that it is not too large for the insert. The chimney should also be checked to ensure it meets the minimum standard of the National Fire Protection Associa- tion (NFPA) Standard 211. The following bullets list the more critical requirements for a properly constructed chimney:

The masonry wall of the chimney, if brick or modular block, must be a minimum of 4 inches (102mm) nominal thickness. A chimney of rubble stone must be at least 12 inches (305mm) thick

The chimney must have a fire clay flue liner (or equiva- lent) with a minimum thickness of 5/8” (16mm) and must be installed with refractory mortar. An equivalent liner must be a listed chimney liner system or other approved material.

A chimney inside the house must have at least 2 inches (51mm) of clearance to the combustible structure. A chim- ney outside the house must have at least 1 inch (25mm) clearance to the combustible structure. Non-combustible fire stops must be installed at the spaces where the chimney passes through floors and/or ceiling (See Figure 8A and 8B on page 8).

Masonry Chimney

Flue Tile

Mantel

Full Listed

Liner Option

Air-tight Face Seal

Direct Connect

 

Seal Option

Damper Area

Minimum Starter

 

Pipe Option

SEAL DAMPER AREA OR FACE SEAL

Figure 10A - Installation Into Masonry Fireplace

METAL HEAT CIRCULATING MASONRY

The Quadra-Fire 5100-I Insert conforms with the safety standard UL-1482 and ULC S628 (Canada) in all respects and is approved to UL & ULC safety standards for instal- lation and use within a fireplace with masonry chimney, in accordance with NFPA No. 211, with or without a direct flue collar connection. A starter pipe is required into existing chimney.

Mantel

Listed Liner

SEAL DAMPER AREA OR FACE SEAL

NOTE: In Canada, a full reline is required.

Figure 10B - Installation Into Metal Heat Circulating

Showing Use Of Starter Pipe

Page 10

250-1960 Rev B

January 30, 2004

Page 10
Image 10
Hearth and Home Technologies 5100-I Installation Options, Masonry Fireplace Using DIRECT-CONNECT Method