R

5100-I WOOD INSERT

INSTALLATIONS INTO ZERO CLEARANCE FIREPLACES IN MOBILE HOMES

(IN USA ONLY)

1.An outside air inlet must be provided for combustion and must

remain clear of leaves, debris, ice and/or snow. It must be

Spark Arestor Cap

 

unrestricted while unit is in use to prevent room air starvation

 

which can cause smoke spillage and an inability to maintain a

 

fire. Smoke spillage can also set off smoke alarms.

Storm Collar

2. Unit must be secured to the mobile home structure. Remove

Roof Flashing

bolts from each side of insert and use plumbers tape to secure

 

to structure (a washer may be required). Reinstall bolts.

 

3.Unit must be grounded with #8 solid copper grounding wire or

equivalent and terminated at each end with N.E.C. approved

Joist Shield/Firestop

Double Wall

grounding device.

Connector Pipe

4.The factory-built fireplace must meet (UM)84-HUD requirements for outside combustion air supply to the firepalce fire chamber and the chimney must be listed to UL103-HT or a listed UL-1777 full length 6 inch (152mm) diameter liner must be used. It must be equipped with a spark arrestor cap

and the outside air must be installed on the insert. (See Figure 9A and complete installation instructions of page 13.)

5.Refer to page 5 of this manual or the Serial label located on the right side of the insert for clearances to combustibles.

6.Floor protections requirements on page 5 must be followed precisely.

7.Use silicone to create an effective vapor barrier at the location were the chimney or other component penetrates to the exterior of the structure.

8.Follow the chimney and chimney connector manufacturer’s instructions when installing the flue system for use

in a mobile home.

NOTE: Offsets from the vertical, not exceeding 45°, are allowed per Section 905(a) of the Uniform Mechanical Code (UMC). Offsets greater than 45° are considered horizontal and are also allowed, providing the horizontal run does not exceed 75% of the vertical height of the vent. Construction, clearance and termination must be in compliance with the UMC Table 9C. This installation must also complies with NFPA 211.

NOTE: Top sections of chimney must be removable to allow maximum clearance of 13.5’ (405cm) from ground level for transportation purposes.

9.Burn wood only. Other types of fuels may generate poisonous gases (e.g., carbon monoxide).

Cover from rear of stove is secured to front of stove

See complete instructions on page 13

CAUTION: THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED. (i.e., DO NOT CUT THROUGH FLOOR JOIST, WALL STUD, CEILING TRUSS, ETC.)

WARNING: DO NOT INSTALL IN SLEEPING ROOM.

Remove 2 Spring Handles

Figure 9A - Installing Outside Air

WARNING: NEVER DRAW COMBUSTION AIR FROM A WALL, FLOOR OR CEILING CAVITY OR FROM ANY ENCLOSED SPACE SUCH AS AN ATTIC OR GARAGE.

January 30, 2004

250-1960 Rev B

Page 9

Page 9
Image 9
Hearth and Home Technologies 5100-I installation instructions Installations Into Zero Clearance Fireplaces in Mobile Homes