7 Accessories

7 Accessories

A. Gas Log/Lighter Provisions

A certified gas log lighter or decorative gas log set can be installed in this fireplace.

This fireplace was not teste3d and listed for use with an un- vented gas log heater. Do not install an unvented gas log heater in this fireplace and operate it with the flue damper in the closed position unless the unvented gas log heater has been specifically tested and listed for use in this fireplace by Underwriters Laboratories Inc.

Use of an unvented gas log heater in this factory built fireplace may create a fire hazard that can result in a structure fire.

Maximum input is 100,000 BTU/hr.

Decorative gas appliance must be certified to ANSI Z21.60 “Standard for Decorative Gas Appliances for Installation in Vented Fireplaces”.

Must be installed in accordance with the National Fuel

Gas Code, ANSI Z223.1.

A log set must incorporate a gas shutoff.

Log set requires the damper to be locked fully open. Knockouts are provided on both sides of the fireplace and in refractories for 1/2 in. (13 mm) iron pipe.

We recommend you seal refractory around pipe with fireplace mortar or cement.

Repack insulation from the knockout around the pipe.

Maintain 1-1/2 in. (38 mm) air space around the pipe for 4 in. (102 mm) beyond the fireplace.

See Figure 7.1.

Gas Code, ANSI Z223.1. WARNING

Asphyxiation Risk

Damper must be locked open when gas logs installed.

Gas fire generates fumes.

Manual background WARNING

Fire Risk

For use with solid wood fuel or decorative gas appliance only.

DO NOT install unvented gas logs.

Manual background WARNING

Fire Risk

Explosion Risk

Inspect appliance and components for damage. Damaged parts may impair safe operation.

Do NOT install damaged components.

Do NOT install incomplete components.

Do NOT install substitute components

Report damaged parts to dealer.

Firebox

Refractory Manual backgroundManual backgroundManual backgroundManual backgroundManual background

Seal with Manual backgroundManual backgroundManual background fireplace mortar Manual backgroundManual backgroundManual background or cement Manual backgroundManual backgroundManual background

Gas Line

Repack

Insulation

Knockout

Outer Shell

of Fireplace

Manual background Maintain air clearance Manual background to combustibles.

Combustible

Materials

 

 

 

 

 

 

 

 

 

 

 

1-1/2 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(38 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Line

 

 

 

 

 

air space

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Combustible materials

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

may be located at zero

 

 

 

 

 

 

 

 

 

 

 

 

clearance to gas line

 

 

 

 

 

 

 

 

 

 

 

 

beyond 4 in. (102 mm)

 

 

 

4 in.

 

 

from fireplace side.

 

 

 

 

 

 

(102 mm)

 

 

 

 

 

 

Figure 7.1 Gas Line Installation

22

Heat & Glo LifeStyles Collection • Montana • 4039-150 Rev I • 08/06