Heat Controller, Inc.DXM2 UNIT CONTROLS Application, Operation, & Maintenance Manual

 

 

 

 

Functional Troubleshooting (cont.)

 

 

 

 

 

 

ESD - ERV Fault (DXM Only)

X

X

ERV unit has fault

Troubleshoot ERV unit fault

 

Green Status LED Code 3

(Rooftop units only)

 

 

 

 

 

 

 

 

 

 

 

No Fault Code Shown

X

X

No compressor operation

See 'Only Fan Operates'

 

X

X

Compressor overload

Check and replace if necessary

 

 

 

 

 

 

 

 

X

X

Control board

Reset power and check operation

 

 

X

X

Dirty air filter

Check and clean air filte r

 

 

X

X

Unit in 'Test Mode'

Reset power or wait 20 minutes for auto exit

 

Unit Short Cycles

X

X

Unit selection

Unit may be oversized for space - check sizing for actual

 

 

load of space

 

 

 

 

 

 

 

 

 

 

 

 

 

X

X

Compressor overload

Check and replace if necessary

 

 

X

X

Thermostat position

Insure thermostat set for heating or cooling operation

 

 

X

X

Unit locked out

Check for lockout codes - reset power

 

Only Fan Runs

 

 

 

 

 

X

X

Compressor overload

Check compressor overload - replace if necessary

 

 

X

X

Thermostat wiring

Check thermostat wiring at DXM2 - put in Test Mode and

 

 

jumper Y1 and R to give call for compressor

 

 

 

 

 

 

 

 

 

 

 

 