Heat Controller Performance Troubleshooting, DXM2 UNIT CONTROLS, Heat Controller, Inc, Symptom

Models: DXM2

1 28
Download 28 pages 2.61 Kb
Page 26
Image 26

Application, Operation, & Maintenance Manual

DXM2 UNIT CONTROLS

Heat Controller, Inc.

Performance Troubleshooting

Symptom

Htg

Clg

Possible Cause

Solution

 

 

 

 

 

 

X

X

Dirty filter

Replace or clean

 

 

 

 

 

 

 

 

Rduced or no air flow

Check for dirty air filter and clean or replace

 

X

 

 

 

 

Check fan motor operation and airflow restrictions

 

 

in heating

 

 

 

 

 

 

 

Too high of external static - check static vs blower table

 

 

 

 

 

 

 

Reduced or no air flow

Check for dirty air filter and clean or replace

 

 

X

Check fan motor operation and airflow restrictions

 

 

in cooling

 

 

 

Too high of external static - check static vs blower table

 

 

 

 

Insufficient Capacity/

 

 

 

Check supply and return air temperatures at the unit and at

X

X

Leaky duct work

distant duct registers if significantly different, duct leaks

Not Cooling or Heating

 

 

 

are present

Properly

X

X

Low refrigerant charge

Check superheat and subcooling per chart

 

X

X

Restricted metering device

Check superheat and subcooling per chart - replace

 

 

X

Defective reversing valve

Perform RV touch test

 

X

X

Thermostat improperly located

Check location and for air drafts behind stat

 

X

X

Unit undersized

Recheck loads & sizing check sensible clg load and heat

 

pump capacity

 

 

 

 

 

X

X

Scaling in water heat exchanger

Perform Scaling check and clean if necessary

 

 

 

 

 

 

X

X

Inlet water too hot or cold

Check load, loop sizing, loop backfill, ground moisture

 

 

 

 

 

 

 

 

 

Check for dirty air filter and clean or replace

 

X

 

Reduced or no air flow

Check fan motor operation and airflow restrictions

 

 

in heating

Too high of external static - check static vs blower table

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

Reduced or no water flow

Check pump operation or valve operation/setting

High Head Pressure

 

 

in cooling

Check water flow adjust to proper flow rate

 

X

Inlet water too hot

Check load, loop sizing, loop backfill, ground moisture

 

 

 

X

 

Air temperature out of range in

Bring return air temp within design parameters

 

 

heating

 

 

 

 

 

 

 

 

 

 

 

X

Scaling in water heat exchanger

Perform Scaling check and clean if necessary

 

X

X

Unit over charged

Check superheat and subcooling - reweigh in charge

 

X

X

Non-condensables insystem

Vacuum system and reweigh in charge

 

X

X

Restricted metering device

Check superheat and subcooling per chart - replace

 

X

 

Reduced water flow

Check pump operation or water valve operation/setting

 

 

Plugged strainer or filter - clean or replace

 

 

in heating

 

 

 

Check water flow adjust to proper flow rate

 

 

 

 

 

X

 

Water temperature out of range

Bring water temp within design parameters

 

 

 

 

 

Low Suction Pressure

 

 

Reduced air flow

Check for dirty air filter and clean or replace

 

 

X

Check fan motor operation and airflow restrictions

 

 

in cooling

 

 

 

Too high of external static - check static vs blower table

 

 

 

 

 

 

X

Air temperature out of range

Too much cold vent air - bring entering air temp within

 

 

design parameters

 

 

 

 

 

X

X

Insufficient charge

Check for refrigerant leaks

 

 

 

 

 

Low Dischage Air

X

 

Too high of air flow

Check fan motor speed selection and airflow chart

Temperature in Heating

 

 

 

 

X

 

Poor performance

See “Insufficient Capacity”

 

 

 

 

X

Too high of air flow

Check fan motor speed selection and airflow chart

High Humidity

 

X

Unit oversized

Recheck loads and sizing check sensible clg load and

 

 

heat pump capacity

 

 

 

 

 

X

X

Thermostat wiring

Check G wiring at heat pump. Jumper G and R for fan

 

operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

Jumper G and R for fan operation. Check for Line voltage

 

X

X

Fan motor relay

across blower relay contacts.

Only Compressor Runs

 

 

 

Check fan power enable relay operation (if present)

 

 

 

 

 

 

X

X

Fan motor

Check for line voltage at motor. Check capacitor

 

 

 

 

 

 

X

X

Thermostat wiring

Check thermostat wiring at or DXM2. Put in Test Mode

 

and then jumper Y1 and W1 to R to give call for fan,

 

 

 

 

 

 

 

 

compressor and electric heat.

 

 

 

 

 

 

 

 

 

Set for cooling demand and check 24VAC on RV coil.

Unit Doesn't Operate in

 

X

Reversing Valve

If RV is stuck, run high pressure up by reducing water flow

 

and while operating engage and disengage RV coil voltage

 

 

 

Cooling

 

 

 

to push valve.

 

 

X

Thermostat setup

For DXM2 check for “O” RV setup not “B”.

 

 

X

Thermostat wiring

Check O wiring at heat pump. DXM2 requires call for

 

 

compressor to get RV coil “Click.”

 

 

 

 

 

 

 

 

 

 

 

 

Improper output setting

Verify the AO-2 jumper is in the 0-10V position

Modulating Valve

X

X

No valve output signal

Check DC voltage between AO2 and GND. Should be O

 

 

 

when valve is off and between 3.3v and 10v when valve

Troubleshooting

 

 

 

 

 

 

is on.

 

 

 

 

 

 

 

No valve operation

Check voltage to the valve

 

 

 

 

Replace valve if voltage and control signals are present at

 

 

 

 

the valve and it does not operate

 

 

 

 

 

26

Page 26
Image 26
Heat Controller Performance Troubleshooting, DXM2 UNIT CONTROLS, Application, Operation, & Maintenance Manual, Symptom