Heat Controller RAD-183A 29Room Air Conditioner, Troubleshooting Guide, Possible Trouble

Models: RAD-183A RAD-243A

1 38
Download 38 pages 39.8 Kb
Page 29
Image 29
29Room Air Conditioner

Troubleshooting Guide

Possible Trouble 2

The compressor does not operate.

Is settingNO

Temp. set lower than Room Manual background • Select the setting Temp. to lower Number. Temp.-0.5°C?

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the voltage No.10

 

NO

Is the voltage N0.7 of

 

NO

Is the Unit for 3 minutes

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of IC01M 0V?

 

 

 

IC01M DC 5V?

 

 

 

delay?

 

YES

 

 

 

 

YES

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check the RY-COMP.

 

 

 

• Exchange IC01M.

 

 

 

• Wait 3 Minutes.

Check the wiring Diagram.

• Exchange MAIN

PCB Ass'y.

Possible Trouble 3

The compressor always operate.

Is the wire connection of

NO

 

• Connect LEAD Wire to

 

 

 

 

RY-COMP again.

 

 

 

 

 

RY-COMP all right?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

• Check the RY-COMP.

29Room Air Conditioner

Page 29
Image 29
Heat Controller RAD-183A, RAD-243A service manual 29Room Air Conditioner, Troubleshooting Guide, Possible Trouble