Heat Controller RAD-183A 33Room Air Conditioner, Troubleshooting Guide, Complaint, Cause, Remedy

Models: RAD-183A RAD-243A

1 38
Download 38 pages 39.8 Kb
Page 33
Image 33
33Room Air Conditioner

Troubleshooting Guide

COMPLAINT

CAUSE

REMEDY

 

 

 

 

Compressor will not run,

Thermostat

Check the position of knob If not at the coldest set-

but fan motor runs.

 

ting, advance the knob to this setting and restart

 

 

 

unit.

 

 

 

Check continuity of the thermostat. Replace ther-

 

 

 

mostat if circuit is open.

 

 

 

 

 

 

Thermistor

Check the TEMP control. If not at the lowest num-

 

 

 

ber, set TEMP control to this setting and restart

 

 

 

the unit. Check the continuity of the thermistor.

 

 

 

Replace the thermistor if the circuit is open.

 

 

 

 

 

 

Capacitor (Discharge

Check the capacitor.

 

 

capacitor before servicing.)

Replace if not within ±10% of manufacturers rat-

 

 

 

ing. Replace if shorted, open, or damaged.

 

 

 

 

 

 

Compressor

Check the compressor for open circuit or ground. If

 

 

 

open or grounded, replace the compressor.

 

 

 

 

 

 

Overload

Check the compressor overload, if externally

 

 

 

mounted. Replace if open. (If the compressor tem-

 

 

 

perature is high, remove the overload, cool it, and

 

 

 

retest.)

 

 

 

 

Compressor cycles on

Voltage

Check the voltage.

overload.

 

If not within limits, call an electrician.

 

 

 

 

 

 

Overload

Check overload, if externally mounted.

 

 

 

Replace if open. (If the compressor temperature is

 

 

 

high, remove the overload, cool, and retest.)

 

 

 

 

Compressor cycles on

Fan motor

If not running, determine the cause. Replace if

overload.

 

required.

 

 

 

 

 

 

Condenser air flow restric-

Remove the cabinet. inspect the interior surface of

 

 

tion

the condenser; if restricted, clean carefully with a

 

 

 

vacuum cleaner (do not damage fins) or brush.

 

 

 

Clean the interior base before reassembling.

 

 

 

 

 

 

Condenser fins (damaged)

If condenser fins are closed over a large area on

 

 

 

the coil surface, head pressures will increase,

 

 

 

causing the compressor to overload. Straighten

 

 

 

the fins or replace the coil.

 

 

 

Compressor cycles on

Capacitor

Test capacitor.

overload.

Wiring

Check the terminals. If loose, repair or replace.

 

 

 

 

 

 

Refrigerating system

Check the system for a restriction.

 

 

 

Insufficient cooling or heat-

Air filter

If restricted, clean of replace.

ing

 

 

Exhaust damper door

Close if open.

 

 

 

 

 

 

 

 

Unit undersized

Determine if the unit is properly sized for the area

 

 

 

to be cooled.

 

 

 

Excessive noise

Turbo or fan

Check the set screw or clamp. If loose or missing,

 

 

 

correct. If the turbo or fan is hitting air guide,

 

 

 

rearrange the air handling parts.

 

 

 

 

 

 

Copper tubing

Remove the cabinet carefully and rearrange tubing

 

 

 

not to contact cabinet, compressor, shroud, and

 

 

 

barrier.

 

 

 

 

33Room Air Conditioner

Page 33
Image 33
Heat Controller RAD-183A, RAD-243A service manual 33Room Air Conditioner, Troubleshooting Guide, Complaint, Cause, Remedy