9 Chase Installations
A. Construct the Chase | Gas line holes and other openings should be caulked with | |||
A chase is a vertical boxlike structure built to enclose the | high temperature caulk or stuffed with unfaced fiberglass | |||
insulation. If the fireplace is being installed on a cement | ||||
fireplace and/or its vent system. Vertical chimneys that | ||||
slab, we recommend that in cold climates, a sheet of |
| |||
run on the outside of a building must be installed inside a |
| |||
plywood or other raised platform be placed underneath to | ||||
chase. | ||||
prevent conducting cold up into the room. |
| |||
Construction of the chase may vary with the type of build- |
| |||
Three examples of chase applications are shown in Fig- | ||||
ing. These instructions are not substitutes for the require- | ||||
ure 9.2. |
|
| ||
ments of local building codes. Local building codes MUST |
|
| ||
|
|
| ||
be checked. |
|
|
| |
1. Fireplace and chimney enclosed in an exterior chase. |
| |||
A chase should be constructed in the manner of all |
| |||
2. Chimney offset through exterior wall and enclosed in chase. | ||||
outside walls of the home to prevent cold air drafting | ||||
3. Chase constructed on roof. |
| |||
problems. The chase should not break the outside build- |
| |||
|
|
| ||
ing envelope in any manner. All outer walls need to be | Note: In cooler climates, all chase walls should be insulated. | |||
insulated. |
|
|
| |
Building codes require false ceiling and ceiling firestops |
|
|
| |
at each floor of the chase or every 10 ft (3.05 m) of clear |
|
|
| |
space to control spread of fire. |
|
|
| |
Walls, ceiling, base plate and cantilever floor at the first |
|
|
| |
level of the chase should be insulated. See Figure 9.1. |
|
|
| |
Vapor and air infiltration barriers should be installed in the |
|
|
| |
chase as per regional codes for the rest of the home. Ad- |
|
|
| |
ditionally, Hearth & Home Technologies recommends that | 1 | 2 | 3 | |
the inside surfaces be sheet rocked and taped (or the use | ||||
of an equivalent method) for maximum air tightness. |
|
|
|
|
|
| Figure 9.2 | Chase Constructions |
Round Termination Cap |
|
|
| |
Metal Chase Top |
| WARNING! You must install false ceilings and ceiling | ||
| firestops at each floor of the chase or every 10 ft (3.05 m) | |||
|
|
| ||
| Ceiling |
| to control spread of fire. | |
| Firestop |
|
|
|
|
|
| WARNING! Risk of Fire! DO NOT seal area between fire | |
|
|
| stop opening and chimney pipe. Restricting air flow around | |
|
|
| chimney may cause fire. | |
|
|
| WARNING! Risk of Fire! You must maintain a minimum | |
|
|
| 2 in. (51 mm) air space clearance to insulation and other | |
| False Ceiling |
| materials surrounding the chimney system. | |
| Attic |
| • Insulation and other materials must be firmly secured to | |
|
| prevent accidental contact with chimney system. | ||
Tabs | Insulation |
| ||
Shield |
| • The chase must be properly blocked to prevent blown | ||
|
| |||
| Ceiling | Insulation in the | insulation or other combustibles from entering and | |
| Firestop | outside walls | making contact with fireplace or chimney. | |
| of the chase | |||
|
| • Failure to prevent contact between insulation or other | ||
Insulation | Insulation |
| ||
False Ceiling | False Ceiling |
| materials and chimney system may cause overheating | |
| and fire. |
| ||
| Chimney |
|
| |
|
|
|
| |
Figure 9.1 | Chase Assembly |
|
|
|
32 |
| Heatilator • CL36D, CR36D • 12538 • Rev V • 05/09 |