A. Hearth Extension

A hearth extension must be installed with all fireplaces to protect the combustible floor in front of the fireplace from both radiant heat and sparks. See Figures 8.1-8.5.

 

High temperature

 

 

 

 

(300°F min.) continuous,

 

 

HX3 or HX4

non-combustible sealant

Fireplace

 

non-combustible material

Protective

insulation

Hearth Ext

Tile, stone or other

 

 

or equivalent

 

 

 

 

 

 

(see Table below)

 

 

 

Metal Hearth

 

 

 

 

Strip

 

 

2 in. (51 mm)

 

 

Floor constructed of wood or

required

 

 

other combustible material

 

 

 

Figure 8.1 Hearth Extension Construction

Figure 8.1 Hearth Extension Construction WARNING

Fire Risk

Metal hearth strips MUST be installed. Sparks or embers may ignite flooring.

This fireplace has been tested and approved for use with a hearth extension insulated to a minimum R value of 1.03.

To substitute materials for the factory-available hearth ex- tensions, calculate insulation alternatives as per Table 8.1 and the following formulas:

Minimum 1 in. overlap

Metal strips are placed 2 in. (51 mm) under the front of the fireplace and must extend beyond the front and sides of fireplace opening by 2 in. (51 mm).

Figure 8.2 Positioning the Protective Metal Hearth Strips

Material WARNING

Fire Risk

Hearth extensions must be installed exactly as specified.

High temperatures or hot embers may ignite concealed combustibles.

Thermal conductivity per inch thickness = k

k = (BTU)(inch) / (foot2)(hour)(°F)

Required thickness = Rk

Thermal resistance per inch thickness = r

r = (foot2)(hour)(°F) / (BTU)(inch)

Required thickness = R / rB.

Table 8.1

Hearth Extension Insulation Alternatives-Total minimum R Value must equal 1.03

 

 

 

Minimum

 

k per inch

r per inch

thickness

Material

thick

thick

required

Hearth & Home HX3, HX4 (Micore 300™)

0.49

2.06

1/2 in.

USG Micore 160™

0.39

2.54

1/2 in.

USG Durock™ Cement Board

1.92

0.52

2 in.

 

 

 

 

Cement Mortor

5.0

0.20

5-1/8 in.

Common Brick

5.0

0.20

5-1/8 in.

 

 

 

 

Ceramic Tile

12.50

0.08

12-1/4 in.

Armstrong™ Privacy Guard Plus

0.46

2.18

1/2 in.

 

 

 

 

Marble

14.3-20.0

0.07-0.05

14-5/8 in. - 20-3/8 in.

30