Laying procedure

Technical guide

 

Laying procedure

 

 

 

 

 

 

 

 

For conductive, dissipative and antistatic floorcoverings

For residential sheet products

Technical

guide

174

Antistatic products

Normal laying using high performance acrylic adhesive which has low water content. The flooring has antistatic properties of its own. These properties do not depend on the laying method used. Copper strips are not necessary.

Dissipative products and conductive products

There are two laying systems:

with conductive adhesive and conductive primer,

on a copper strip grid with a high-performance acrylic adhesive which has low water content. Copper strips: code 0584

Width: 1 cm

Average length: 250 lm

Thickness: 6/100 mm

Weight: about 3.6 kg

LAYING PROCEDURE FOR CONDUCTIVE FLOORING

WITH CONDUCTIVE ADHESIVE AND CONDUCTIVE PRIMER

The sheets must be unrolled and left in the room to be covered, with the adhesive, for at least 24 hours prior to laying.

Laying procedure Minimum ambiant temperature must be 15 °C.

1.Apply a conductive primer.

The coverage should be 100-150 g/m2.

Leave to dry for at least 12 hours.

2.1 Sheets

Lay first length along guide line, ensuring sheets are laid lengthways in the same direction as the light falls.

2.2 Tiles

Trace a perpendicular

Trace a line

line to this axis

perpendicular to the

ensuring equal cuts for

main entrance.

tiles on both sides.

3.Use 2 lm of copper strips for every 30 m2 for earthing. Connect the copper strip to the earth (1 earth for every 30 m2).

For rooms over 30 m2, lay copper strips at the periphery of the room and on the diagonal.

4.Adhering with acrylic single stick conductive adhesive

(type Cégé 100 Conductrice - Akzo-Nobel) and a sharp-serrated notche, or similar approved adhesive. The coverage should be approximately 200-300 g/m2.

In order to achieve a regular and appropriate coverage change the spatula regularly.

For residential sheet products Carefully follow the manufacturer's instructions when applying primer and adhesive. Ensure that the supplier can provide a 10 year guarantee for the conductibility of the adhesive.

5.1 Lay the sheets.

5.2 Lay the tiles.

6. Smooth down

7. Groove and heat weld the joints 24 hours

manually then roll

after installation (compulsory).

with a 50 kg flooring

Dried adhesive on surface of flooring may be

roller.

removed with alcohol or turpantin.

 

 

Do not traffic the floorcovering for

 

 

 

48 hours after installation.

LAYING PROCEDURE FOR RESIDENTIAL SHEET PRODUCTS

Check that the subfloor on which you intend to lay the floorcovering is smooth, free from grit, grease and wood treatments. Most of these floorcoverings should not be laid over damp areas although Texline and Griptex have higher tolerances for damp. Please refer to the Technical Department for further advice.

The floorcovering should be placed in the room where it is due to be laid for at least 2 hours prior to laying. The temperature should no less that 18oC.

If you plan to lay two or more widths please ensure sufficient material is purchased to allow for pattern match.

Sheet lengths should be reversed laid.

Most installations can be safely loose laid whilst ensuring that exposed edges that may be kicked up (such as doors and joints) are securely adhered to the floor using an 8 to 10cm width application of Gerflor E120 adhesive. Joints should be treated with Gerflor Cold Weld Liquid SG916 to ensure a strong bond. We recommend threshold strip to be fitted to doorways.

For permanent installations or where heavy domestic furniture such as washing machines are likely to be moved around, the floor covering can be fully adhered to the subfloor.