CHAPTER 4 SETTING

 

Rotary switch

Dip switch

C O D E

TYPE

4.1 POSITION OF SETTING SWITCH

 

Figure 4-1shows position of setting switch.PAC, DIV,

 

BIN, BCD which printed around the dip switch (TYPE)

 

means one time input , 2 dividing input, binary input, BCD

 

input.

 

Figure 4-1 Position of switch

4.2 INITIAL SETTING CONDITION OF PRINTED BOARD

Table 4-2 shows initial setting condition

Table 4-2 Initial setting condition

(Setting condition at shipment).

 

 

 

 

 

Setting item

Switch No.

Initial setting

 

 

 

condition

 

 

2

PAC (OFF)

 

 

 

 

 

 

1

BIN (OFF)

 

 

 

 

4.3 SETTING OF INVERTER

Rotary switch

0 to ￿

0

CODE

 

 

Table 4-3 shows setting items of the inverter (SJ300, L300 series) related to operating SJ-DG.

Make sure to refer to “CHAPTER 3 OPERATION”, “CHAPTER 4 EXPLANATION OF FUNCTION” of the instruction manual of the inverter, and set exactly.

Table 4-3 Table of setting items of inverter related to SJ-DG

Code

Function name

Data range

Initial data

Possible

Possible mode

Note

 

 

 

 

 

 

setting at

of change at

 

 

 

 

 

 

 

operating

operating

 

 

Setting frequency

00(VR)/01(terminal)/02(operator)

02 (SJ300)

 

 

 

A001

/03(RS485)/04(option1)

X

X

-

destination

 

00 (L300P)

 

 

/05(option2)

 

 

 

 

 

 

 

 

 

 

 

 

 

One selection

of

00(remote)/01(option1)

 

 

 

 

P031

acceleration

and

00

X

O

-

/02(option2)

 

 

deceleration time

 

 

 

 

 

 

 

 

 

 

 

 

 

Selection of torque

00(4quadrant individual setting)

 

 

 

Only

B040

/01(terminal

switch)/02(analog

00

X

O

limit

 

SJ300

 

 

input)/03(option1)/04(option 2)

 

 

 

 

 

 

 

 

 

 

P032

Selection

of

00(remote)/01(option1)

00

X

O

Only

position command

/02(option2)

 

SJ300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)In case of setting frequency, make sure to set frequency command destination (A001) to option.

(2)In case of setting acceleration and deceleration time, make sure to set acceleration and deceleration time 1 selection (P031) to option.

(3)In case of setting torque limit, make sure to set torque limit selection (B040) to option.

(4)In case of setting position, make sure to set selection of position command (P032) to option.

4.4INPUT MODE BY DIP SWITCH AND ROTARY SWITCH

6

Page 12
Image 12
Hitachi SJ-DG Position of Setting Switch, Initial Setting Condition of Printed Board, Setting of Inverter