2-10. Electrical Service Guide

NOTE

All values calculated at 40% duty cycle.

Input Voltage

230

 

 

Input Amperes at Rated Output

67

 

 

Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes

100

 

 

Min Input Conductor Size In AWG/Kcmil

8

 

 

Max Recommended Input Conductor Length In Feet (Meters)

166 (51)

 

 

Min Grounding Conductor Size In AWG/Kcmil

8

 

 

Reference: 1996 National Electrical Code (NEC)

S-0092-J

 

 

2-11. Connecting Input Power

Tools Needed:

YHave only qualified persons make this installation.

YSpecial installation may be required where gasoline or volatile liquids are present – see NEC Article 511 or CEC Section 20.

Units come equipped with input

GND/PE power cord for installation into line disconnect device. Select type and size overcurrent protection using Section 2-10.

GND/PE

 

Connect first. L1

L2

ST-802 238

OM-355 Page 13

Page 17