9-4. Overload Protection (Kohler-Powered Units)
Tools Needed:
3/8 in
1
2
YStop engine.
.If the unit is extremely over-
loaded, weld and generator pow- er will stop. Turn unit off and re- start to reset the generator protection circuit and restore weld and generator power out- put.
If the rated output of the unit is ex- ceeded, engine speed may vary rapidly until the weld or generator power load is reduced.
1Circuit Breaker CB4 (See Parts List)
CB4 protects the generator excitation circuit. If CB4 opens, there will be no/low weld and generator power output.
Press button to reset breaker.
2 Fuse F6 (See Parts List)
F6 protects the engine wiring harness. If F6 opens, the engine does not crank. If F6 opens while the engine is running, the engine stops.
Replace fuse if open. Reinstall panel before operating unit.
. If a fuse or circuit breaker opens,
it usually indicates a more seri- ous problem exists. Contact a Factory Authorized Service Agent.
Ref. 801
9-5. Servicing Optional Spark Arrestor (Kohler-Powered Units)
Y Stop engine and let cool.
1 Spark Arrestor Screen
Clean and inspect screen. Replace spark arrestor if screen wires are broken or missing.
1
Tools Needed:
1/4 in
Ref. 801