SECTION 7 − OPERATING AUXILIARY EQUIPMENT

NOTE

If the unit is extremely overloaded, weld and generator power will stop. Turn unit off and restart to reset the generator protection circuit and restore weld and generator power output.

If the rated output of the unit is exceeded, engine speed may vary rapidly until the weld or generator power load is reduced.

The welding generator provides power while welding and with the Amperage control in any position. However, under these conditions equipment connected to the welding generator may be subject to larger than normal voltage fluctuations. It is recommended that only lamps be powered under these conditions.

7-1. Standard Receptacles

1

4

 

 

 

 

Y If unit does not have GFCI re-

 

 

 

 

 

ceptacles, use

GFCI-

 

 

 

 

 

protected extension cord.

 

 

 

 

1

120/240 V 50 A AC Recep-

 

 

 

 

 

tacle RC1

 

 

 

 

 

RC1 supplies 60 Hz single-phase

 

 

 

 

power at weld/power speed. Maxi-

5

2

6

3

mum output is 10 kVA/kW.

 

2

120 V 20 A AC Duplex Recep-

 

 

 

 

 

 

 

 

 

tacle RC2

 

 

 

 

 

3

120 V 20 A AC Duplex Recep-

 

 

 

 

 

tacle RC3

 

RC2 and RC3 supply 60 Hz single- phase power at weld/power speed. Maximum output from RC2 or RC3 is 2.4 kVA/kW.

4 Circuit Breaker CB1

CB1 protects the ac receptacles from overload. If CB1 opens, the ac receptacles do not work.

. Move CB1 toggle switch to On position to reset circuit break- er. If breaker continues to open, contact Factory Authorized Service Agent.

5Circuit Breaker CB2

6Circuit Breaker CB3

CB2 protects RC2 and CB3 pro- tects RC3 from overload. If a circuit breaker opens, the receptacle does not work.

.Press button to reset circuit breaker. If breaker continues to

open, contact Factory Authorized Service Agent.

Combined output of all receptacles limited to 10 kVA/kW rating of the generator.

EXAMPLE: If 20 A is drawn from each 120 V duplex receptacle, only 21 A is available at the 240V receptacle:

2 x (120 V x 20 A) + (240 V x 21 A) = 10 kVA/kW (approx.).

202 069-A

OM-945 Page 20

Page 24