2.2.3 Locating the Room Thermostat
While still in the Test Mode, as described in section 2.2.2, the room thermostat should be located taking the following into consideration and reviewing the illustrations below:
1.Find a suitable location where the signal transmission is reliable. Reliable transmission is indicated when the receiver box is flashing the green LED every 6 seconds. NOTE: The receiver box relay will be off.
2.Install the room thermostat EITHER on the wall using the wall bracket OR attach the optional table stand as shown in below.
3.Exit the Test Mode by moving the setting slider to the required operating mode (AUTO or OFF).
Wall bracket | Table stand |
•The room thermostat should be installed in an open space for best performance as it is a radio frequency device.
•Leave at least 30cm distance from any metal objects including wall boxes and at least 1 metre from any other electrical equipment eg. radio, TV, PC etc.
•Do not mount onto metal wall boxes. • It is recommended that the receiver box is fully installed.
2.3 System Check
Now a simple test can be completed to check the full system has been installed correctly:
1.Set the slider switch to the OFF mode.
2.Check the boiler supply is on and check that the green LED on the receiver box is off.
3.Set the slider switch to the MAN mode.
4.Adjust the setpoint up to the maximum (35°C) by pressing the button. The boiler should come on (green LED ON on receiver box) after a few seconds and the symbol appears on the room thermostat LCD display.
5.Set the slider switch to the OFF mode. The boiler will go off (green LED OFF on receiver box) after a few seconds and the symbol disappears.
6.Check the system operation by moving the slider between MAN and OFF modes several times, bearing in mind the switching delay referred to above.
Now, you should have completed the installation successfully - to begin operating at the default factory settings move the slider to the AUTO mode or select PROG to modify the