4.3 Using the Room Thermostat for Specific Applications
The CM927/921 RF room thermostat is a versatile controller that can be used to control many different applications. For most typical applications, like
Specific Application: | Setting: |
| What to change: |
|
| |
|
|
|
|
| ||
|
| Cycle/ | Minimum ON | Note: All parameters listed below belong to category 2 | ||
|
| Hour | Time | - System Parameters (see Installer Parameters Table) | ||
|
|
|
|
|
|
|
HEATING | Gas Boiler (<30kW) | 6 | 1 | No changes required |
|
|
|
|
|
|
|
|
|
| Oil Boiler | 3 | 4 | Set 1:Ot parameter to 4 |
|
|
|
|
|
| Set 2:Cr parameter to 3 |
|
|
|
|
|
|
|
|
|
| Thermal Actuator | 12 | 1 | Set 2:Cr parameter to 12 |
|
|
|
|
|
|
|
|
|
| Zone Valve | 6 | 1 | No changes required |
|
|
|
|
|
|
|
|
|
| Electric Heating | 12 | 1 | Set 2:Cr parameter to 12 |
|
|
| (resistive load <8A) |
|
| Set 3:EH parameter to 1 |
|
|
|
|
|
|
|
| |
AIR- |
|
|
| To enable switching between cooling and heating |
| |
CONDITIONING |
|
|
| modes adjust parameter 4:HC in category 2 (0 = |
| |
|
|
|
| disabled, 1 = enabled). Now you can switch between | ||
|
|
|
| these modes by pressing the | and buttons |
|
|
|
|
| together for 5 seconds in any of the product operating | ||
|
|
|
| modes (AUTO, MAN or OFF). Explain to the end user | ||
|
|
|
| how to switch between these modes using the | and | |
|
|
|
| buttons and ensure the cooling program is modified | ||
|
|
|
| as required. |
|
|
|
|
|
|
|
|
|
| Heat Pump / Air- | 3 | 4 | Set 1:Ot parameter to 4 |
|
|
| Conditioner |
|
| Set 2:Cr parameter to 3 |
|
|
|
|
|
|
|
|
|
| Fan Coil | 6 | 1 | No changes required |
|
|
|
|
|
|
|
|
|
4.4 Using the Special Features of the Room Thermostat
Special Feature: | Description: | Enable/Disable |
|
|
|
Optimisation | The thermostat will adjust the start time in the morning/afternoon so the | To enable: Set parameter 8: |
(Variable Start | desired temperature is reached by the start of the program period. The | OP (category 1) to 1. |
Time) | system will restrict the start time to a max of 2 hours. |
|
|
|
|
Heating or Cooling | This product can be used for heating or cooling applications. If you select | To enable: Set parameter 4: |
Operation | cooling mode the control algorithm and factory default program will be | HC (category 2) to 1. |
| modified. You can independently modify the heating and cooling profile. |
|
|
|
|
Summer/Winter | This feature moves time automatically on the last Sunday of March and | To enable: Set parameter 3: |
Auto time change | the last Sunday of October. The feature is factory enabled. | tC (category 1) to 1. |
|
|
|
Temperature Offset | If the thermostat is located in a particularly hot/cold location for reliable | Set parameter 12:tO |
| signal transmission reasons then the measured/displayed temperature | (category 1) to the required |
| can be adjusted by +/- 3°C. This is useful if the homeowner wants the | offset value. |
| reading to match another appliance temperature display. |
|
|
|
|
Upper/Lower | The normal upper temperature limit of 35°C can be reduced to 21°C | Set parameter 6:uL (category |
Temperature Limit | to save the homeowner energy. The normal lower limit of 5°C can be | 1) to the desired upper limit. |
| increased up to 21°C to protect inhabitants from cold. | Set parameter 7:LL (category |
|
| |
|
| 1) to the desired lower limit. |
|
|
|
CM900 Wireless - Programmable Room Thermostat |