IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide

To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displayed telling the user that this step is being executed. When complete, the message "DONE" is displayed to indicate the file was successfully uploaded.

Note: If critical configuration changes were made, such as the mode of operation, the communicator will reset to ensure that the programming features are enabled.

If the file is not successfully uploaded, one of the following prompts will be displayed. Follow the steps shown below until the upload is successful.

 

Display

Description

What to do

 

 

 

Communicator is not yet initialized.

Wait for RSSI indicator LEDs to be lit.

 

Cannot Upload

 

 

Try Again? Y/N_

 

 

Press [Y].

 

 

 

 

 

 

 

Network problem, or you answered "N" to

Initiate the Force Server Update

 

Failed to Update

 

 

Root File!

 

"Cannot Upload Try Again?" prompt.

Command by pressing the [0] key.

 

 

 

 

 

Setting Factory Defaults

To reset the programming options to factory-default values, at the "Exit Prog Mode?" prompt press [Shift] plus [ESC]. Note, setting the factory defaults will also erase any password that may have been entered.

Set Default? Y/N_

Press [Y] to reset factory default values. Press [N] to cancel this function.

Press [Shift] then [Y], then [#]. The Create Password prompt appears, follow the prompts then exit.

STEP 6 – Configure the Fire Panel

1.Ensure the Phone Line Supervision (or Telco Fault) on the panel is enabled. Then choose a setting that is no higher than 90 seconds (or as close to that as the panel allows).

2.Ensure no more than 1 pause character (usually a comma) is programmed into the dialing string (usually 2 seconds). Note, this is necessary since the Dialer Capture Module waits only 3 seconds after the phone number is dialed. Having more than 3 seconds of pause time will cause it to think the phone number is complete and cause it to generate the high-low tones at an incorrect moment.

STEP 7 – Test the System

1.Close the 1451-UL9 Wired Transformer enclosure, then close and lock the cabinet cover.

2.Refer to the fire panel's installation/operation guide for the testing procedure.

3.(Notify the monitoring station that a test will be conducted.) Test the system to ensure it is operating.

4.Verify communications with the monitoring station is successful by sending several events. Also, get confirmation that these events were received.

8

Page 10
Image 10
Honeywell IPGSM-4GC manual Configure the Fire Panel, Test the System

IPGSM-4GC specifications

The Honeywell IPGSM-4GC is an advanced cellular communicator designed for security applications, providing reliable communication for alarm systems. This device enhances the ability of security systems to transmit signals to monitoring centers, ensuring that alarms are promptly addressed. With the increasing reliance on cellular technology, the IPGSM-4GC stands out as an essential tool for both residential and commercial security solutions.

One of the main features of the IPGSM-4GC is its dual-path communication capability. It can transmit signals via both Ethernet and cellular networks, providing redundancy that enhances reliability. In the event of an internet outage, the device seamlessly switches to cellular communication, ensuring that the alarm system remains operational at all times. This dual-path feature is particularly valuable in critical security applications where continuous communication is necessary.

The IPGSM-4GC also supports 4G LTE technology, which offers faster response times and improved signal quality compared to previous generation communicators. This technology enables the device to communicate with monitoring stations more efficiently, ensuring that alarm signals are sent and received quickly. Additionally, with 4G LTE being the current standard, the IPGSM-4GC is designed to remain relevant as older technologies are phased out.

Security is further enhanced by the robust encryption protocols employed by the IPGSM-4GC. The device uses advanced AES encryption, protecting sensitive data transmitted over cellular networks from potential interception or unauthorized access. This feature is crucial for users looking to maintain a high level of security in their alarm systems.

Installation and integration of the IPGSM-4GC are simplified thanks to its compatibility with a wide range of Honeywell alarm panels. The device utilizes a straightforward setup process, making it accessible for both professional installers and DIY enthusiasts. The modular design allows for easy updates and maintenance, ensuring longevity in performance.

In summary, the Honeywell IPGSM-4GC is a cutting-edge solution that combines dual-path communication, 4G LTE technology, and advanced encryption to provide a reliable and secure cellular communication option for alarm systems. With its ease of installation and compatibility with various Honeywell panels, it serves as a vital component for modern security solutions, meeting the demands of today’s connected world.