Honeywell IPGSM-4GC manual Wiring the 659EN Line Fault Monitor Required for ULC

Models: IPGSM-4GC

1 24
Download 24 pages 5.21 Kb
Page 8
Image 8

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide

Wiring the 659EN Line Fault Monitor (Required for ULC)

The IPGSM-4GC is compatible with Fire Panels when the model 659EN Line Fault Monitor, (also known as the HFS- 659EN), is installed. Note, the wire colors may vary.

1.Refer to the installation guide for the 659EN.

2.Mount the 659EN on the lower left side of the IPGSM-4GC cabinet.

3.DO NOT cut the 659EN’s BLACK Output Relay Jumper or the BLUE Voltage Trip Threshold Jumper.

4.Complete the interface wiring as shown below:

YEL

 

to Dialer Capture Module, Terminal, Tip 2

 

ORG

 

 

to Dialer Capture Module, Terminal, Ring 2

 

 

RED

 

to Power Boost 1, Terminal, OUTPUT 1, DC+

 

BLK

 

to Power Boost 1, Terminal, OUTPUT 1, DC-

 

GRN

 

to Power Boost 1, Terminal, ERTH GND

 

659EN

Wire to a

Zone on the Fire Panel

4.7K, 1/2 watt

IPGSM-4GC

IPGSM-4GC-013-V0

Example wiring for an addressable fire control panel:

IPGSM-4GC

Commercial Fire Communicator

 

 

 

 

 

 

 

 

YEL

 

 

to Dialer Capture Module, Terminal, Tip 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORG

 

 

to Dialer Capture Module, Terminal, Ring 2

 

 

 

 

 

 

 

 

 

RED

 

 

to Power Boost 1, Terminal, OUTPUT 1, DC+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

 

 

to Power Boost 1, Terminal, OUTPUT 1, DC-

 

 

 

 

 

 

 

 

 

GRN

 

 

to Power Boost 1, Terminal, ERTH GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

659EN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

47K, 1/2 watt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIRE LITE Addressable Fire Alarm Control Panel MS-9050UD

 

 

 

 

 

 

- To next device

 

 

 

 

 

 

TOP

 

 

 

 

 

+ on SLC Loop

 

 

 

 

 

 

 

 

 

 

 

MMF-300A

 

 

 

 

 

Braided-shield/Drain

Monitor Module

 

 

 

 

 

Wire

 

 

 

 

 

 

T11

 

 

 

 

 

T10

 

 

 

T1

 

T9

 

 

 

T2

 

T8

 

 

 

T3

 

T7

 

5 6 7 8 9 10

5 6 7 8 9

T4

 

T6

4

11

4

T5

 

3

12

3

 

 

2 1 0 151413

2 1 0

 

 

 

 

TENS

ONES

 

 

LOOP

 

 

 

ADDRESS

 

B+

B-

 

Shield

TB2

 

 

TB5

 

 

B+ A+ B- A- A B

NO NC C

 

 

 

SLC Loop

RELAY 1

 

 

 

ALARM CONTACTS

 

 

 

 

 

IPGSM-4GC-014-V0

6

Page 8
Image 8
Honeywell IPGSM-4GC manual Wiring the 659EN Line Fault Monitor Required for ULC