IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide

STEP 5 – Program the Communications Module

You must use the 7720P Programming tool to program the IPGSM-DPC.

When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to accept the displayed default value (xxx) or enter the new value and press the [#] key for the next prompt. Use the [Space] key to scroll through a list of options.

1.

(no display)

Connect the 7720P.

2.

7720P PROGRAMMER

Press [#].

3.Strt Prog Mode? Y/N

4.Program Device? Y/N

5.Com Path Choice (IP&GSM)

6.Primary City ID (??)

7.Primary CS ID (??)

 

8.

 

Primary Sub ID (????)

 

 

 

 

 

 

 

 

 

 

9.Use DHCP? Y/N (Y)

10.NIC IP Address: 255.255.255.255

11.Subnet Mask: 255.255.255.255

12.Gateway IP Address: 255.255.255.255

13.DNS Serv IP Addr: 255.255.255.255

14.Review? Y/N

15.Create Password? Y/N

16.Exit Prog Mode? Y/N

17.DONE

Press [Shift] then [Y], then [#].

Press [Shift] then [Y], then [#].

Press [Space] to scroll choices; IP&GSM, IP, or GSM. At choice, press [#].

Enter number 01-99, then press [#].

Enter number 01-FE, then press [#].

Enter number 0001-9999, then press [#].

Note: If a Com Path Choice of IP&GSM or IP was selected, prompt 9 will appear.

If your router is configured for DHCP, press [Shift] then [Y], then press [#].

Note: If DHCP is not selected (your router is set for a static IP), prompts 10 through 13 will appear.

Enter choice, then press [#]. Follow the prompts.

Enter choice, then press [#]. Follow the prompts.

Enter choice, then press [#]. Follow the prompts.

Enter choice, then press [#]. Follow the prompts.

Enter choice, then press [#]. Follow the prompts.

Enter choice, then press [#]. Follow the prompts.

Press [Shift] then [Y], then press [#].

Notes: If an error in programming occurs, set the factory defaults (see next topic) and reprogram.

The IP Fault Time, and the GSM Fault Time are each fixed at 1 minute and are not programmable.