L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS

Table 11. Troubleshooting Guide

System

Diagnostic

 

 

Condition

Condition

Check

Action

 

 

 

 

Boiler is hot,

Display is ON.

120 Vac at C1-C2

120 Vac at C1-C2, check wiring to pump.

house is cold.

 

 

Wiring OK, is pump running?

 

 

 

If not, replace the pump.

 

 

 

If pump is running, check for trapped air or

 

 

 

closed zone valves.

 

 

 

 

 

 

Boiler below the Low Limit

 

 

temperature, wait for boiler to go

 

 

 

above Low Limit temperature.

 

 

 

 

 

 

 

Boiler above LL? If yes, check for

If no 120 Vac, replace control.

 

 

120 Vac between ZC and L2.

If yes, check zone relays, circulators and

 

 

 

wiring.

 

 

 

 

 

 

ELL setting (L7248L only)

Set ELL to Off for multizone system (see Fig.

 

 

 

11).

 

 

 

Set ELL to On for External Low Limit (see

 

 

 

Fig. 13).

 

 

 

 

 

 

Boiler above LL? If yes, check 120

If no 120 Vac, check C1-C2 (see above).

 

 

Vac at ZR-L2 (only L7248L with

If yes, check the External Low Limit control.

 

 

ELL set On)

 

 

 

 

 

Boiler is hot,

Display is ON.

Boiler Demand signal from the

24 Vac on T-T (or 0 Vac on ZR-L2), check

no hot potable

 

water heater (either 120 Vac at

wiring to water heater

water.

 

ZR-L2, or 0 Vac on T-T; depends

Wiring OK, check the water heater

 

 

on installation and “duu” setting)

 

 

 

 

 

 

 

“duu” setting

Set duu to ON if 120 Vac water heater

 

 

 

demand is connected to ZR

 

 

 

Set duu to OFF if open/closed water heater

 

 

 

demand is connected to T-T

 

 

 

 

 

 

Check DHW Module and DHW

DHW Module not properly connected and/or

 

 

Sensor

DHW Sensor improperly positioned

 

 

 

 

ZONE 2

TO ADDITIONAL R845A

 

 

RELAYS FOR OTHER ZONES

 

CIRCULATOR

 

 

 

 

 

1

L1

L7224

 

L2 (HOT)

R845A RELAY ZONE 2

 

 

6

 

 

 

5

 

 

 

3

 

SENSOR

 

 

 

 

4

 

 

 

1

 

 

ZR

 

 

L1

 

 

LINE

2

 

 

 

VOLTAGE

L2

 

 

CIRCULATOR

C2

 

ZONE 2

 

 

 

 

 

LOW VOLTAGE

 

B2

 

THERMOSTAT

 

 

 

 

1 POWER SUPPLY. PROVIDE DISCONNECT

LINE

C1

 

MEANS AND OVERLOAD

VOLTAGE

B1

PROTECTION AS REQUIRED.

OIL BURNER

 

RELAY

ZC

 

 

 

 

 

2 CONTROL CASE MUST BE CONNECTED

 

 

TO EARTH GROUND. USE GROUNDING

 

 

SCREW PROVIDED.

 

 

 

 

LOW

 

VOLTAGE

2

THERMOSTAT

T

T 3

2

1

LINE

M27115

Fig. 9. L7224A,C multizone system with circulator connections.

11

68-0281EFS—05

Page 11
Image 11
Honeywell L7224A,C, L7248A,C,L Condition, If no 120 Vac, replace control, Set ELL to On for External Low Limit see